Field Settings; When 2 Units Are Installed In 1 Room - Daikin BA-Series Service Manual

Inverter pair floor / ceiling suspended dual type ba-series
Table of Contents

Advertisement

Field Settings

4. Field Settings

4.1

When 2 Units are Installed in 1 Room

Outline
When 2 indoor units are installed in 1 room, 1 of the 2 indoor units and the corresponding
wireless remote controller can be set for different addresses.
Both the indoor unit PCB and the wireless remote controller need alteration.
Indoor Unit PCB
Caution
Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
Wireless Remote
Controller
115
Cut the address setting jumper JA on the control PCB.
Cut the address setting jumper.
EXIST
CUT
ADDRESS JA
EXIST
CUT
Address
1
2
SiBE05-722ED
1
2
(R12419)
Jumper
(R14202)
Trial Operation and Field Settings