3.6

Freeze-up Protection Control

During cooling operation, the signal sent from the indoor unit controls the operating frequency
limitation and prevents freezing of the indoor heat exchanger. (The signal from the indoor unit is
divided into zones.)
The operating frequency limitation is judged with the indoor heat exchanger temperature.
3.7

Heating Peak-cut Control

During heating operation, the indoor heat exchanger temperature determines the frequency
upper limit to prevent abnormal high pressure.
The operating frequency limitation is judged with the indoor heat exchanger temperature.
Function and Control
13˚C
Reset zone
A˚C
Up zone
B˚C
Keep zone
C˚C
Dropping zone
0˚C
Stop zone
A (°C)
B (°C)
C (°C)
7
5
B˚C
C˚C
D˚C
Indoor heat exchanger
thermistor temperature
Zone
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
A (°C)
B (°C)
C (°C)
65
56
Indoor heat exchanger
thermistor temperature
3
D (°C)
E (°C)
53
51
46
Control Specification
(R14718)
Stop zone
A˚C
Dropping zone
Keep zone
Up zone
E˚C
Reset zone
(R14645)
Control
46