Toshiba HWS-803XWHM3-E Data Book page 56

Air to water heat pump
Hide thumbs Also See for HWS-803XWHM3-E:
Table of Contents

Advertisement

4.HYDRO UNIT
Cooling capacity and power input
Capacity (kW)
20
27
30
TO
(°C)
35
40
43
Power input (kW)
20
27
30
TO
(°C)
35
40
43
EER
20
27
30
TO
(°C)
35
40
43
* Cooling capacity and power input are the data at rated compressor operating frequency of rated condition 1
* Power input does not include water pump power.
* Cooling capacity and power input are measured in accordance with EN14511.
TO
:
Outdoor temperature (DB°C)
LWT
:
Leaving water temperature (°C)
LWT (°C)
7
10
12.88
14.10
13.44
14.72
12.95
14.18
12.11
13.26
10.87
11.90
10.11
11.14
LWT (°C)
7
10
3.12
3.21
3.93
4.04
4.12
4.23
4.42
4.55
4.74
4.86
4.93
5.09
LWT (°C)
7
10
4.13
4.40
3.42
3.65
3.14
3.35
2.74
2.92
2.30
2.45
2.05
2.19
13
15
15.29
16.49
15.96
17.20
15.38
16.58
14.38
15.05
13.08
13.87
12.29
13.09
13
15
3.28
3.31
4.13
4.22
4.33
4.42
4.65
4.70
4.98
5.05
5.24
5.31
13
15
4.67
4.98
3.87
4.08
3.55
3.75
3.10
3.20
2.63
2.75
2.35
2.47
55
Engineering Data book
18
17.68
18.45
17.77
16.20
14.75
14.07
18
3.35
4.31
4.51
4.80
5.16
5.47
18
5.28
4.28
3.94
3.38
2.86
2.57

Hide quick links:

Advertisement