Toshiba HWS-803XWHM3-E Data Book page 47

Air to water heat pump
Hide thumbs Also See for HWS-803XWHM3-E:
Table of Contents

Advertisement

4.HYDRO UNIT
Heating capacity and input specifications
▼Outdoor unit
Hydro unit
Rated heating capacity and power input
Rated condition 1
LWT=35°C
dT=5deg
Rated condition 2
LWT=45°C
dT=5deg
* Rated heating capacity and power input are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Heating capacity and power input are measured in accordance with EN14511.
TO
:
Outdoor temperature (DB°C) RH85%
LWT
:
Leaving water temperature (°C)
dT
:
Delta temperature (deg)
Leaving water temperature - return water temperature
HWS-1403H8-E, HWS-1403H8R-E
HWS-1403XWH**-E
Capacity
kW
Power input
kW
COP
W/W
Rated water flow rate
/min
Capacity
kW
Power input
kW
COP
W/W
Rated water flow rate
/min
14.0
3.21
4.36
40.1
14.0
4.12
3.40
40.1
46