8. OUTDOOR UNIT INSTALLATION MANUAL
„ Optional Installation Parts
(Locally procured)
Parts name
Refrigerant piping
A
Liquid side: Ø9.5 mm
Gas side: Ø15.9 mm
Pipe insulating material
B
(polyethylene foam, 10 mm thick)
C
Putty, PVC tape
„ Refrigerant Piping
Connection
TAKE NOTE OF THESE 4 IMPORTANT POINTS
BELOW FOR PIPING WORK
1. Keep dust and moisture away from inside the
connecting pipes.
2. Tightly connect the connection between pipes
and the unit.
3. Evacuate the air in the connecting pipes using a
VACUUM PUMP.
4. Check for gas leaks at connection points.
Piping connection
Liquid side
Outer diameter
Ø9.5 mm
Gas side
Outer diameter
Ø15.9 mm
Flaring
1. Cut the pipe with a pipe cutter.
Be sure to remove burrs that may cause a gas leak.
2. Insert a flare nut into the pipe, and then flare the
pipe. Use the flare nuts supplied with the air to water
heat pump or those for R410A.
Insert a flare nut into the pipe, and flare the pipe.
As the flaring sizes of R410A differ from those of
refrigerant R22, the flare tools newly manufactured
for R410A are recommended.
However, the conventional tools can be used by
adjusting the projection margin of the copper pipe.
Q'ty
One each
1
One each
CAUTION
Thickness
0.8 mm
Thickness
1.0 mm
Projection margin in flaring: B (Unit: mm)
Rigid (Clutch type)
Outer diam. of
copper pipe
9.5
15.9
Flaring diameter size: A (Unit: mm)
Outer diam. of copper pipe
9.5
15.9
* In case of flaring for R410A with the conventional
flare tool, pull the tool out approx. 0.5 mm more than
that for R22 to adjust it to the specified flare size.
The copper pipe gauge is useful for adjusting the
projection margin size.
Piping necessary to change the flare nut/
machining size due to pipe compression
▼ Flare nut width: H and flare matching size: A.
Flare nut width: H
Copper pipe
outer dia.
H
For R410A
For R22
Flare machining size: A
A
Copper pipe
outer dia.
For R410A
For R22
Becomes a little larger for R410A
Do not apply refrigerator oil to the flare surface.
– 147 –
Engineering Data book
B
R410A tool used Conventional tool
R410A
1.0 to 1.5
0 to 0.5
A
+0
A
–0.4
13.2
19.7
Ø6.4
Ø9.5
Ø12.7
Ø15.9
17
22
26
Same as above
24
Ø6.4
Ø9.5
Ø12.7
Ø15.9
9.1
13.2
16.6
9.0
13.0
16.2
used
(mm)
Ø19.0
29
36
Same
27
as
above
(mm)
Ø19.0
19.7
24.0
19.4
23.3

Hide quick links: