4.HYDRO UNIT
Average heating capacity and power input
Capacity (kW)
-20
-15
-7
-2
2
TO
(°C)
7
10
12
15
20
Power input (kW)
-20
-15
-7
-2
2
TO
(°C)
7
10
12
15
20
COP
-20
-15
-7
-2
2
TO
(°C)
7
10
12
15
20
* Heating capacity and power input are include defrost cycle data.
* Heating capacity and power input are shown at maximum compressor operating frequency
* Power input does not include water pump power.
* Heating capacity and power input are measured in accordance with EN14511.
TO
:
Outdoor temperature (DB°C) RH85%
LWT
:
Leaving water temperature (°C)
30
35
3.93
3.83
4.66
4.54
5.45
5.30
6.24
6.11
6.86
6.75
9.02
8.78
9.56
9.29
10.11
9.81
10.94
10.60
12.42
11.99
30
35
1.70
1.82
1.78
1.90
2.06
2.21
2.10
2.26
2.11
2.28
1.87
2.07
1.84
2.03
1.83
2.02
1.83
2.02
1.82
2.01
30
35
2.32
2.11
2.62
2.38
2.64
2.40
2.98
2.70
3.26
2.96
4.82
4.25
5.20
4.58
5.52
4.86
5.98
5.25
6.82
5.97
LWT (°C)
40
45
3.74
—
4.44
4.27
5.15
4.99
5.97
5.84
6.64
6.52
8.58
8.34
9.10
8.84
9.62
9.35
10.41
10.13
11.82
11.50
LWT (°C)
40
45
1.90
—
2.00
2.13
2.33
2.47
2.39
2.56
2.43
2.60
2.25
2.46
2.21
2.42
2.20
2.41
2.20
2.41
2.18
2.44
LWT (°C)
40
45
1.97
—
2.22
2.00
2.21
2.02
2.50
2.29
2.73
2.50
3.82
3.39
4.12
3.65
4.37
3.88
4.73
4.20
5.42
4.71
27
Engineering Data book
50
55
—
—
—
—
4.84
—
5.69
5.55
6.47
6.38
8.11
7.87
8.42
8.29
8.92
8.87
9.68
9.52
11.03
10.78
50
55
—
—
—
—
2.79
—
2.86
3.14
2.88
3.17
2.65
2.85
2.61
2.86
2.60
2.87
2.60
2.88
2.58
2.91
50
55
—
—
—
—
1.73
—
1.99
1.77
2.25
2.02
3.06
2.76
3.23
2.90
3.43
3.09
3.72
3.31
4.28
3.70