(Items necessary to perform the applied control at the local site are described.)
DN
Item
01
Filter sign lighting
0000 : None
time
0002 : 2500H
0004 : 10000H
02
Dirty state of filter
0000 : Standard
03
Central control
0001 : No.1 unit
address
0099 : Unfixed
04
Specific indoor unit
0000 : No priority
priority
06
Heating temp shift
0000 : No shift
0002 : +2°C
0d
Existence of
0000 : Provided
automatic cool/heat
mode
0F
Cooling only
0000 : Heat pump
10
Type
0000 : (1-way air discharge cassette)
0001 : (4-way air discharge cassette) to 0037
11
Indoor unit capacity
0000 : Unfixed
12
Line address
0001 : No.1 unit
13
Indoor unit address
0001 : No.1 unit
14
Group address
0000 : Individual
0002 : Follower unit of group
19
Flap type
0000 : Not provided
(Adjustment of air
0004 : [4-way Air Discharge Cassette type] and [Under Ceiling type]
direction)
1E
Temp difference of
0000 : 0 deg
automatic cooling/
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
heating mode
selection COOL →
HEAT, HEAT →COOL
28
Automatic reset of
0000 : None
power failure
29
Operation condition
0000 : Usual
of humidifier
(Detection control for heat exchanger temperature)
2A
Selection of option/
0000 : Filter input
error input (CN70)
0002 : Humidifier input
2E
HA terminal (CN61)
0000 : Usual
select
30
Automatic elevating
0000 : Unavailable
grille
31
Ventilating fan
0000 : Unavailable
control
32
TA sensor selection
0000 : Body TA sensor
33
Temperature unit
0000 : °C (at factory shipment)
select
40
Control for humidifier
0000 : None
(+ drain pump control)
0002 : Humidifier + Ultrasonic system
0003 : Humidifier + Natural drain system (Pump OFF)
5d
High ceiling selection
[4-way Air Discharge Cassette type] and [Under Ceiling type]
(Air volume selection)
0000 : Standard filter
0001 : Super-long life
[Concealed Duct Standard type]
0000 : Standard static pressure
0003 : High static pressure 2
60
Timer set
0000 : Available (Operable)
(Wired remote
controller)
62
Smudging-proof
0000 : Clear
control clear
92
Outside interlock
0000 : Operation stop
release condition

Table: Function selecting item numbers (DN)

Description
to
to
to
to
to
(Standard,
Oil guard panel)
(Pump ON after specified time passed) (Unused)
(40Pa)
(100Pa)
0001 : 150H
0003 : 5000H
0001 : High degree of dirt
(Half of standard time)
0064 : No.64 unit
0001 : Priority
0001 : +1°C
0010 : +10°C
(Up to +6 recommended)
0001 : Not provided
(Automatic selection from
connected outdoor unit)
0001 : Cooling only
(No display of [AUTO] [HEAT])
0001 to 0034
0030 : No.30 unit
0064 : No.64 unit
0001 : Header unit of group
0001 : Swing only
0010 : 10 deg
0001 : Reset
0001 : Condition ignored
0001 : Alarm input (Air washer, etc.)
0001 : Leaving-ON prevention control
0001 : Available
(Auto grille, Oil guard,
Auto grille panel)
0001 : Available
0001 : Remote controller sensor
0001 : °F
0001 : Humidifier + Vaporizing system
(Pump ON)
0001 : High static pressure 1
(70Pa)
0005 : Correspond to quiet sound
0006 : Low static pressure (20Pa)
0001 : Unavailable (Operation prohibited)
0001 : Release communication signal
receive
75
At shipment
According to type
0000 : Standard
0099 : Unfixed
0000 : No priority
0002 : +2°C
(Floor type 0000: 0°C)
0001 : Not provided
0000 : Heat pump
According to model type
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
According to type
0003 : 3 deg
(Ts±1.5)
0000 : None
0000 : Usual
0002 : Humidifier
0000 : Usual
(HA terminal)
0000 : Unavailable
0000 : Unavailable
0000 : Body TA sensor
0000 : °C
0003 : Humidifier ON,
Pump OFF
0000 : Standard
0000 : Available
4- way Air Discharge
Cassette type only
0000 : Operation stop

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Super mmu-ap0121hSuper mmu-ap0151hSuper mmu-ap0271hSuper mmu-ap0301hSuper mmu-ap0361hSuper mmu-ap0481h ... Show all

Table of Contents