8-7-3. Error Clearing Function
1. Clearing from the main remote controller
[Error clearing in outdoor unit]
Error of the outdoor unit is cleared by the unit of one refrigerant circuit system to which the indoor units oper-
ated by the remote controller. (Error of the indoor unit is not cleared.)
For clearing errors, the service monitor function of the remote controller is used.
<Method>
1
Change the mode to service monitor mode by pushing
4 seconds or more.
2
Using
/
The display in Section A in the following figure is counted with interval of 5 seconds as
0005
0004
" → → → → → "
" → → → → → "
"
When the count arrives "
∗ However, counting from "
3
When
button is pushed, the status returns to the normal status.
Operation procedure
1
2
3
The status returns to the normal status.
Section A
[Error clearing in indoor unit]
Error in the indoor unit is cleared by
(Only error of the indoor unit connected with operating remote controller is cleared.)
buttons, set "FF" to item code.
0003
0002
" → → → → → "
" → → → → → "
0000
", the error is cleared.
0005
" is repeated on the display.
3
1
SET
button on the remote controller.
+
CL
0001
0000
" → → → → → "
".
CODE No.
UNIT No.
R.C.
No.
UNIT
CL
118
buttons simultaneously for