Procedure 3 : Writing-in of setup contents to EEPROM
(The EEPROM contents which are installed on the service P .C. board have been set up at shipment from the factory.)
1. Push
+
+
SET
CL
ALL
(
is displayed in the UNIT No box.)
10
In this time,
is displayed in the item code (DN). The fan of the indoor unit operates, and also starts
swinging in a model with flap.
2. Using temperature setup
3
one by one.
3. First set up the type and capacity code of the indoor unit.
(The data at shipment from the factory is written in EEPROM by changing the type and capacity code.)
10
1) Set
to the item code (DN). (As before)
2) Using the timer time
(For example, 0001 indicates 4-way Air Discharge Cassette type.): Refer to the attached table.
3) Push
button. (OK if display goes on.)
SET
4) Using temperature setup
5) Using the timer time
(For example, 0012 indicates 80 class.): Refer to the attached table.
6) Push
button. (OK if display goes on.)
SET
7) Push
button to return to the normal stop status.
4. In the next, the contents such as address setup, which were set up at the local site after installation are
written in EEPROM. Execute again the operation in the above item 1).
5. Using temperature setup
(Lighting time setup for filter sign)
6. Compare the contents of the setup data which is displayed in this time with contents noted in a memo in
Procedure 1 and customer's information.
1) If data is incorrect, change it using the timer time
noted in a memo, and then push
2) Do nothing if data is same as those in the memo.
7. Using temperature setup
Check also the contents of the setup data and then change them it to those in the memo.
8. Then repeat operations in items 6. and 7.
9. After setup operation, push
In a group operation, turn off the power supply once, return the group wires between indoor units and CN41
connectors as before, and then turn on power of all the indoor units.
(It requires approx. 1 minute to operate the remote controller.)
∗ The item code (DN) is consisted with
Even if pushing
SET
change by pushing
<EEPROM layout>
EEPROM (IC10) is attached to IC socket. To remove it, use a pair of tweezers, etc. To attach EEPROM, arrange
the direction as shown in the following figures.
∗ In exchanging time, pay attention not to bend the lead wire of IC.
P .C. board (MCC-1402)
EPROM (IC10)
buttons simultaneously for 4 seconds or more.
/
buttons, the item code (DN) can be moved one step up 1 or down
/
buttons, set up the type.
5
/
buttons, set
/
buttons, set up the capacity code.
/
buttons, set
button. (OK if display goes on.)
SET
/
buttons, change the item code (DN).
button to return to the normal stop status.
01
AA
to
button after changing the data incorrectly, the data can be returned to one before
button before changing the item code (DN).
CL
P .C. board (MCC-1403)
1
4
11
to the item code (DN).
01
to the item code (DN).
/
buttons so that it matches with contents
. DN No. may jump on the way.
EPROM (IC10)
Align notch directions of IC socket
and EEPROM for installation.
IC socket