Toshiba Super MMU-AP0091H Service Manual page 146

Super modular multi
Hide thumbs Also See for Super MMU-AP0091H:
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check code
Sub-code
controller
P26
P26
01: Compressor 1 side
02: Compressor 2 side
P29
P29
01: Compressor 1 side
02: Compressor 2 side
P31
Detected
AI-NET
Check code name
position
central control
remote controller
14
IPDU
G-Tr short-circuit
protection error
16
IPDU
Compressor
position detection
circuit error
47
Indoor
Other indoor error
(Group follower
unit error)
Status
Error detection condition
All stop
Instantaneous over-current
was detected when compres-
sor started.
All stop
Position was not normally
detected.
Corresponding
E07/L07/L03/L08 was
unit only stops.
detected when other indoor
unit in the group was defective.
Check item (position)
• Check connector connection and wiring on IPDU P .C. board.
• Check compressor error and defect of compressor coil.
• Check outdoor P .C. board (IPDU) error.
• Check connector connection and wiring.
• Check compressor error and defect of compressor coil.
• Check P .C. board (IPDU) error.
• Check indoor P .C. board.