General Venting
Sidewall Venting Options – Direct Vent Installation
Figure 4-3(a)

Two-pipe Termination (Sidewall)

Exhaust must terminate a
minimum of 18" above Air-inlet
termination; see Figure 4-5(a) for
more details.
Exhaust
3" IPEX Concentric Termination
illustrated, see Figure 4-5(b) for
more details.
Inlet
Exhaust
18
3" IPEX Low Profile Termination
illustrated; see Figure 4-5(c) for
more details.
Inlet
Figure 4-3(c)

Concentric Termination (Sidewall)

3" DuraVent Concentric
Termination illustrated, see
Figure 4-5(d) for more details.
Figure 4-3(b)

Low Profile Termination (Sidewall)

Exhaust
Exhaust
Tx I&O Manual
Inlet