Fault Finding Chart 6

6
Does controller display
„AUTO‟?
NO
(Manual mode)
Is auxiliary(s) turned on?
YES
Is EIB cable plugged into
correct socket on main
controller?
YES
Is EIB cable continuous
and unbroken?
YES
Fault Finding Chart 7
7
Does heater function
using main controller?
YES
Temporarily connect
a new remote controller.
TM018 Raypak 131 Type A Pool & Spa Heaters REV: A
D.O.I: 8/04/2009
This document is stored and maintained electronically by
YES
(Auto mode)
For information on programming
auxiliary operation in auto mode
refer to „TM055 Raypak Pool Heater
Controller Guide‟.
For information on selecting
auxiliary‟s whilst in manual mode;
refer to „TM055 Raypak Pool Heater
Controller Guide‟.
YES
Correct socket is marked „E.I.B.‟
Temporarily connect
a new EIB.
Is remote controller cable
plugged into correct socket
on main controller?
YES
YES
Service. All printed copies not bearing this statement in RED are deemed "uncontrolled"
Is controller clock set to
correct time?
YES
Are auto mode time
periods programmed
correctly?
YES
Are auxiliary's
programmed to turn on
during auto mode time
periods?
NO
NO
Does auxiliary(s) operate
using new EIB?
NO
NO
Correct socket is marked „Remote‟
NO
Is remote controller cable
continuous and unbroken?
Does heater operate using
new remote controller?
NO
32
Set controller clock to correct
NO
time.
Correctly program auto mode
NO
time periods.
Auxiliary(s) must be
NO
programmed to turn on during
auto mode time periods.
Plug EIB cable into correct
socket on main controller.
Replace EIB cable.
YES
Replace EIB.
Recover temporarily
connected new EIB and
replace main controller.
1
Plug remote controller cable
into correct socket on main
controller.
Replace remote controller
NO
cable.
YES
Replace remote controller.
Recover temporarily
connected new remote
controller and replace main
controller.