Raypak 131 Service Instructions Manual page 39

Tm020
Table of Contents

Advertisement

Fault Finding Tests 16 – 19
Using a multimeter on the AC voltage
scale, measure between the brown wire
terminal and the blue wire terminal on relay
1.
The following result should be obtained:
24 Volts AC.
Using a multimeter on the AC voltage
scale, measure between each purple wire
and the blue wire on the RAM ignition
module terminal strip.
The following results should be obtained:
st
purple wire – blue wire: 24 Volts AC.
1
nd
purple wire – blue wire: 24 Volts AC.
2
TM018 Raypak 131 Type A Pool & Spa Heaters REV: A
D.O.I: 8/04/2009
This document is stored and maintained electronically by
Test 16
Test 18
Disconnect wiring at 55ºC outlet high limit
and using a multimeter on the ohms scale,
measure between the two terminals on the
55ºC outlet high limit.
The following result should be obtained:
0 ohms (high limit contact closed).
Using a multimeter on the AC voltage
scale, measure between the brown wire
and the blue wire on the RAM ignition
module terminal strip.
The following result should be obtained:
24 Volts AC.