Function
DHW-storage
Parameter depending on hydraulic system!
Charge push forward time
Flow setpoint boost
Transfer boost
Type of charging
Recharging | Full charging | Full charging legio | Full charg 1st. time
day | Full charg 1st time legio. charging
Switching diff
Charging time limitation
Discharging protection
Off | Always | Automatically
Charging temp max
Recooling temperature
Recooling collector
Off | Summer | Always
El imm heater optg mode
Substitute | Summer | Always
Electrical immersion heater release
24h/day | DHW release | Time program 4/DHW
El immersion heater control
External thermostat | DHW sensor
Automatic-Push
Off | On
Excess heat draw
Off | On
With buffer
No |Yes
With prim contr/system pump
No |Yes
With solar integration
No |Yes
Pump speed min
Pump speed max
Speed Xp
Speed Tn
Speed Tv
Transfer strategy
Always | DHW release
Interm circ boost recharging
Intermediate circuit boost
Excess interm circ temp max
Flow setp compensation delay
Flow setp compensation Xp
Flow setp compensation Tn
396532 05.11
Paramount three 30-115 kW
Programming
Prog.
Standard value
1)
Level
no.
5011
E
60 min
5020
E
18°C
5021
E
10°C
5022
E
Full charging
5024
E
4°C
5030
E
120 min
5040
E
Automatic
5050
E
65°C
5055
E
80°C
5057
E
Off
5060
E
Substitute
5061
E
DHW release
5062
E
DHW sensor
5070
E
ON
5085
E
ON
5090
E
Yes
5092
E
Yes
5093
E
Yes
5101
E
0%
5102
E
100%
5103
E
35°C
5104
E
120 s
5105
E
45 s
5130
E
Always
5139
E
5°C
5140
E
2°C
5141
E
2°C
5142
E
30 s
5143
E
60°C
5144
E
30 s
57