Important: The boiler unit is supplied in accordance Any person installing or working on the boiler must with Potterton Commercial quality assurance plan be qualified and attention is drawn to the mandatory registered to meet the requirements of BSN ISO requirements of C.O.R.G.I.
Corrosion Protection/Frost Protection PARAMOUNT in Loft Space: If the PARAMOUNT is used as a loft centre, POTTERTON recommends The combustion air must be free of corrosive installing a water catch pan below the hot-water tank.
Page 8
SECTION 2 POTTERTON COMMERCIAL PRODUCTS DIVISION INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 6 installed in protective zone 2 (see also note above "Operation in wet rooms"). In protection zone 1 and 2, only permanently installed lines are permissible according to VDE 0100.
Page 9
POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 3 INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 7 Applications and Installation Details Application example 1a 1 pumped heating circuit (CTC) with remote room control module RRG (B5) or with boiler mounted control (Hydraulic system “2”) HKM (N3) &...
Page 10
SECTION 3 POTTERTON COMMERCIAL PRODUCTS DIVISION INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 8 Application example 2a 1 constant temperature circuit and one compensated circuit with remote room control module RRG (B5), (Hydraulic system “50”) including hot-water tank temperature WWF Alternatively: 1 CTC with heating circuit module HKM &...
Page 11
(PARAMOUNT 40 ONLY, SEE Fig.1) after filling, are the settings required. move the non-return valve back into the operating position. Check for leakage (max. water test pressure Application example 1a: 3 bar).
Page 12
For lengths longer than specified in the table please contact the Technical Department for suitability Note: Flue sizes shown for the Concentric Vertical Flue are adapted sizes for flues supplied by Potterton Commercial. For flues supplied by other manufacturers, please refer to technical data for standard spigot sizes.
Page 13
POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 3 INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 11 GAS CONNECTION lead to disturbances) otherwise screen cable should be used. Factory Settings: The PARAMOUNT is set at the factory to a maximum heat load either for...
Page 14
SECTION 4 POTTERTON COMMERCIAL PRODUCTS DIVISION INSTALLATION , OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 12 START-UP AND CHECK LIST Important Notes: These instructions should always Start Up: Before commissioning the boiler read the be kept in the boiler room where they are readily operating instructions and observe the “check list”...
POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 4 INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 13 Fig. 5 Commissioning illuminates when burner operation. • Switch on the mains switch (3) on the Note: If an outdoor temperature sensor is not connected the PARAMOUNT is heated up to a boiler boiler module (1).
SECTION 4 POTTERTON COMMERCIAL PRODUCTS DIVISION INSTALLATION , OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 14 Gas/Air Ratio Control: With the gas/air ratio control New settings are taken over immediately by the for the PARAMOUNT, the gas supply is adapted to BMU.
Page 17
INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 15 Fig. 6 gas valve (injector pressure settings can be made with 2.5 mm Allen key) (not provided) Landis & Staefa Co. VDU (PARAMOUNT 40) Kromschröder Co.CG 10…No.847 55 366 (PARAMOUNT 60) Adjustment screw for...
Page 19
POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 4 INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 17 CHECKING VALUES Calling Parameter Values - Proceed as follows to obtain the various parameter values (see Fig. 5 “Control Panel”). Entering the Display Mode - The display mode can...
Page 20
2) Parameters in the group “A” can be selected by momentarily pressing the display mode button. For error messages, see Table 11, or instructions for EUROCONTROL controls 4) Display flashes alternately 5) Internal BMU SW diagnostic code (POTTERTON Customer Service) selection of a few error codes Code No. Explanation...
Page 21
POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 5 INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 19 ADJUSTMENT TABLE FOR HEATING ENGINEERS Table 6 – Setting system dependent parameters in heating engineer level of control centre BMU (with RRG room control module or RRG service module).
Page 22
SECTION 5 POTTERTON COMMERCIAL PRODUCTS DIVISION INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 20 Display on room control module RRG Function Basic Setting Progra BUM parameter final user (set at factory) Setting *) level ZbreMinL Minimum running time for burner.
Page 23
For a list of the internal software diagnosis codes, see RRG manual of the Service Module for a selection of the fault codes see table 6 Parameters only valid if the boiler is equipped with a PWM pump (modulating pump) (Not Potterton supply) The PARAMOUNT boilers are factory-preset to a single step pump (Parameter 561.0 OFF).
Page 24
1 and 2 parallel. If the room temperature setting is depending on type of boiler: not achieved with the heating curve set, this allows PARAMOUNT 40 → 38 kW or adaptation. (See table below) PARAMOUNT 60 → 58 kW or PARAMOUNT 80 →...
Page 25
POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 5 INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 23 545 (ZbreMinP) Minimum pause time for burner: Note: Program nos. 556 and 557 (KonfigRg 2 and 3) The PARAMOUNT is provided with a minimum should not be adjusted! pause time or start-up disable of 2 min.
Page 26
SECTION 5 POTTERTON COMMERCIAL PRODUCTS DIVISION INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 24 Table 9 Assignment of HKM or RRG to the Heating Circuit (Program No.553; KonfigHks) Setting (e.g. Setting Function HC 1 (CTC) HC 2 (VTC) Program Effect of HKM or RRG on HC 1 and HC 2 No.553...
Page 27
POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 5 INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 25 When bit 5 = 0, the pump is generally operated at the circuit 1. This function is independent of summer and minimum pump speed setting program No. 538 winter mode.
Page 28
SECTION 5 POTTERTON COMMERCIAL PRODUCTS DIVISION INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 26 Connect header pump for X1/M5: If hydraulic schematic requires a header pump 623 (PanfoExtSchwelle) Heat output setpoint: The connect its plug to X1/M5. A heating circuit pump relative heat output is given by an analogue signal (CTC) is connected to exit M1.
Page 29
POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 5 INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 27 Quick heat-up: Only possible when room control Anti-Legionnaires disease function (only with module RRG is connected and room sensor active. room control module RRG): Heat-up is started...
Page 30
SECTION 6 POTTERTON COMMERCIAL PRODUCTS DIVISION INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 28 Heating Circuit Module HKM and Room Control Module (Optional Extra) Fig. 7 Heating circuit module HKM Installation position for EMS time clock Heating control Hot water control...
Page 31
POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 6 INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 29 Heating Circuit Module HKM (Fig.7) Supplied setting temperature knob, with the PARAMOUNT thermostatic valves to the desired temperature. Correct again only after the temperature has Operation without Outdoor Temperature Sensor: adapted.
Page 32
SECTION 6 POTTERTON COMMERCIAL PRODUCTS DIVISION INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 30 Fig. 9 Views of Boiler Paramount 40 Ignition Transformer Air Vent (below lid) Ignition and Ionisation Air Silencer Electrode Mixing Chamber Gas Valve Gas Injector Pressure Switch...
Page 33
POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 6 INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 31 Fig 10 Views of Boiler Paramount 60 & 80 Air Vent Ignition Transformer (below lid) Air Silencer Mixing Chamber Ignition and Ionisation Electrode Gas Injector Gas Valve...
Page 34
INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 32 • REMOVING HEAT EXCHANGER Disconnect plug for boiler sensor (flow and return) • Remove Heat Exchanger PARAMOUNT 40 Loosen flow return fittings heat exchanger (flat sealing) • Follow the steps below to completely remove the Disconnect cable from water pressure switch •...
Page 35
POTTERTON COMMERCIAL PRODUCTS DIVISION SECTION 6 INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 33 CONTROL CENTRE Reset: Following Reset (power OFF/ON) the BMU control centre starts in the Home mode. Electrodes: To ensure proper function of the ignition and ionisation, ensure that installation...
Page 36
SECTION 6 POTTERTON COMMERCIAL PRODUCTS DIVISION INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARAMOUNT PAGE 34 FAULT MESSAGES Table 11 Fault Messages (display 13 flashing) Display Description Explanations flashing Possible caused and function sequence (Code No) Outdoor temperature sensor short circuit or discontinuity...
NOTE: It is the installer’s responsibility to ensure that the boiler is correctly commissioned by a competent engineer and that this report is completed and kept as a record. A commissioning service available from Potterton at the address listed on the back page of this manual. When a Potterton engineer commissions, this completed report will be sent to the installer.
Page 48
OPERATIONAL SAFETY CHECKS COMMENTS ON ACCESSIBILITY FOR MAINTENANCE Check control stat operation Check limit stat operation Check high/low stat operation 6.4* Check for gas leaks 6.5* Check for gas leakage past valve assembly 6.5¶ Check for oil leaks Check boiler locks out on loss of flame signal Check boiler locks out on air pressure switch operation Check boiler locks out on all other safety...
Page 50
Web Site: www.pottertoncommercial.co.uk COMMERCIAL SERVICE OFFICES Our service organisation covers the whole of the U.K. to look after your needs for all Potterton Commercial Products. We are also able to offer our services for other manufacturers products. SOUTHERN REGION...