Drain Piping; Refrigerant Piping Work; Flaring The Pipe End - Daikin FTX20GV1B Installation Manual

R410a split series
Hide thumbs Also See for FTX20GV1B:
Table of Contents

Advertisement

6.

Drain piping.

1) Connect the drain hose, as described right.
2) Remove the air filters and pour some water into the drain pan to check the water
flows smoothly.
3) If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end.
[Figure of Hose Front End]
4) When extending the drain hose, use a commercially available
extension hose with an inner diameter of 16 mm.
Be sure to thermally insulate the indoor section of the extension
hose.
5) When connecting a rigid polyvinyl chloride pipe
(nominal diameter 13mm) directly to the drain
hose attached to the indoor unit as with embed-
ded piping work, use any commercially available
drain socket (nominal diameter 13mm) as a
joint.

Refrigerant Piping Work

1.

Flaring the pipe end.

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward
so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
WARNING
1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.
■English
φ16
φ18
φ16
The drain hose provided
to indoor unit.
φ18
The drain hose provided
Commercially available drain
to indoor unit.
socket
(nominal diameter 13mm)
(Cut exactly at
right angles.)
Set exactly at the position shown below.
A
Flare tool for R410A
Clutch-type
A
0-0.5mm
Die
he drain hose should
be inclined downward.
No trap is permitted.
Do not put the end
of the hose in water.
Extension drain hose
Indoor unit
drain hose
Heat insulation tube
(Field supply)
Commercially available rigid
polyvinyl chloride pipe
(nominal diameter 13mm)
Remove burrs
Flaring
Conventional flare tool
Clutch-type (Rigid-type)
Wing-nut type (Imperial-type)
1.0-1.5mm
1.5-2.0mm
Check
The pipe end must
Flare's inner
be evenly flared in
surface must
a perfect circle.
be flaw-free.
Make sure that the
flare nut is fitted.
10