Interior Masonry Chimney Conversions - Lopi Heritage-2000 Owner's Manual

Table of Contents

Advertisement

ADDENDUM #2 Masonry Chimney or Fireplace Conversions
Follow the requirements and use the equipment listed in the illustration to the right to install this
appliance into an interior masonry chimney.
Maximum vertical rise is 38'
Minimum vertical rise is 10'
Use the following restrictor positions:
Position 1 for heights between 10' and 16'
Position 7 for heights between 16' and 38'
NOTE: these restrictor positions are based upon lab tests. The ideal restrictor position may vary.
Interior Masonry Chimney
Standard Masonry Fireplace
The entire chimney system
must be air-tight. Seal the
connector cover and inspect
the chimney.
Make sure the coaxial pipe
maintains a 1" clearance to any
combustible. The vent must be
sealed air-tight.
Travis Industries
Installation Addenda
The entire chimney system
must be air-tight. Make sure to
seal the flashing, clean-out,
and thimble connection, and to
inspect the chimney.
Make sure the coaxial pipe
maintains a 1" clearance to any
combustible. The vent must be
sealed air-tight.
#990 90° Elbow
Co-Axial Straight
Lengths
9 3 5 0 8 1 2 1
#991 High Wind
Termination
Flashing (included in
#934 Masonry
Conversion Kit
#711 Flex Liner (4" dia.)
(or other UL 1777 Gas
Liner)
Connector with Cover
(included in #934 Masonry
Conversion Kit)
#991 High Wind
Termination
Flashing (included in
#934 Masonry
Conversion Kit)
#711 Flex Liner (4" dia.)
(or other UL 1777 Gas Liner)
Connector (included in #934
Masonry Conversion Kit)
secured and sealed to
block-off plate.
37
2 3 1 0 0 0

Hide quick links: