Viessmann VITOTRONIC 300 Installation And Service Instructions Manual page 89

Type gw5b & mw1b, digital boiler control unit & weather-compensated digital cascade control unit
Table of Contents

Advertisement

Vitotronic 300, GW5B & MW1B Installation and Service
"General" Group
Coding in the factory set condition
5F:0
Function input DE3 at extension EA1:
No function.
6E:50
No display correction of the outside
temperature.
76:0
Without LON communication module.
77:5
LON participant number.
78:1
LON communication enabled.
79:1
With LON communication module:
Control unit is fault manager.
7A:0
Without central control of heating circuits.
7B:1
With LON communication module:
Control unit transmits the time.
7F:1
Detached house.
80:6
If a fault occurs for at least
30 s, a fault message is displayed.
81:1
Automatic summer/wintertime changeover.
82:3
Summer time starts:
March
83:5
Summer time starts:
Week 5 of the selected month.
(continued)
Possible change
5F:1
Heating program changeover.
5F:2
External demand with minimum set supply
temperature.
Selection of set value in coding address "9B"
in the "General" group.
5F:3
External blocking.
5F:4
External blocking with fault message.
5F:5
Fault message input.
5F:6
Brief operation, DHW circulation pump
(pushbutton function).
Setting of runtime for DHW circulation pump in
coding address "12" in the "General" group.
6E:0
Display correction –5 K
to
to
6E:49
Display correction –0.1 K
6E:51
Display correction +0.1 K
to
to
6E:99
Display correction +4.9 K
76:1
With LON communication module (automatic
recognition).
77:1
LON participant number, adjustable from 1 to
to
99:
77:99
1 – 4 = Boiler control unit
5 = Cascade control unit
10 – 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
78:0
LON communication disabled.
79:0
Control unit is not fault manager.
7A:1
With central control (see page 66):
System circuit A1 (heating circuit 1).
7A:2
Heating circuit with mixing valve M2
(heating circuit 2).
7A:3
Heating circuit with mixing valve M3
(heating circuit 3).
7B:0
Time not transmitted.
7F:0
Apartment building.
Separate adjustment of holiday program and
time program for DHW heating possible.
80:0
Immediate fault message.
80:2
The minimum fault duration until a fault
to
message is issued is adjustable from 10 to
80:199
995 sec; 1 step
81:0
Manual summer/wintertime changeover.
81:2
Use of the radio clock receiver (automatic
recognition).
81:3
With LON communication module:
The control unit receives the time.
82:1
January to December
to
82:12
83:1
Week 1 to week 5 of the selected month
to
83:5
Code 2, Vitotronic 300-K
5 sec.
89