Viessmann VITOTRONIC 300 Installation And Service Instructions Manual page 85

Type gw5b & mw1b, digital boiler control unit & weather-compensated digital cascade control unit
Table of Contents

Advertisement

Vitotronic 300, GW5B & MW1B Installation and Service
"Heating Circuit 1", "Heating Circuit 2", "Heating Circuit 3" Group
Coding in the factory set condition
Slab curing function (Not used)
F1:0
Slab curing function disabled. (Not used)
Party mode time limit
F2:8
Time limit for party mode or external heating
program changeover via pushbutton: 8 h
Note: Observe settings of coding addresses
"5D", "5E", "5F" in the "General"
group, as well as "D5" and "D8" in the
"Heating circuit..." group.
Start temperature raising
F8:-5
Temperature limit for raising reduced mode
23° F (-5º C); see example on page 67.
Observe the setting of coding address "A3".
End temperature raising
F9:-14
Temperature limit for raising the reduced set
room temperature 7° F (-14º C); see example
on page 67.
Set supply temperature increase
FA:20
Raising the set boiler water or supply
temperature by 20% when changing from
operation with reduced room temperature to
operation with standard room temperature.
See example on page 67.
Duration set supply temperature increase
FB:30
Duration for raising the set boiler water or
supply temperature (see coding address "FA")
60 min.
See example on page 67.
*1
Party mode ends automatically in the "Heating and DHW" heating program when the system changes over to
operation with standard room temperature.
Possible change
F1:1
Only for heating circuits with mixing valve:
to
Slab curing function adjustable in accordance
F1:6
with 6 optional temperature/time profiles.
(Not used)
F1:15
Constant supply temperature 68° F (20° C).
F2:0
No time limit
*1
.
F2:1
Time limit adjustable from 1 to 12 h
to
F2:12
F8:+10
Temperature limit adjustable from
to
+50 to -76° F (+10 to -60° C).
F8:-60
F8:-61
Function disabled.
F9:+10
Limit for raising the set room temperature to
to
the value selected for standard mode adjustable
F9:-60
from +50 to -76° F (+10 to -60° C).
FA:0
Temperature rise adjustable from 0 to 50%.
to
FA:50
FB:0
Duration adjustable from 0 to 300 min;
to
1 step
FB:150
Code 1, Vitotronic 300-K
(continued)
*1
.
2 min.
*1
.
85