Takagi 110U Indoor (T-KJr2U-IN) Installation Manual And Owner's Manual page 19

On-demand water heater
Table of Contents

Advertisement

Maximum delivery capacity of cubic feet of gas per hour of IPS pipe carrying Natural Gas with 0.60 specific gravity
based on pressure drop of 0.5" W.C.
Based on energy content of 1,000 BTU/Cubic ft.: The water heater requires 140 Cubic ft./hr for the 110U (T-KJr2U)
models, 190 Cubic ft./hr for the 310U (T-K4U) models, and 199 Cubic ft./hr for the 510U (T-D2U) models.
Pipe size
Diameter
10'
20'
363
249
3/4"
1"
684
470
1
1,404 965
1/4"
1
2,103 1,445 1,161 993
1/2"
2"
4,050 2,784 2,235 1,913 1,696 1,536 1,413 1,315 1,234 1,165 1,033 936
Gas sizing example
(Natural Gas)
5' Length
1-1/4" Pipe size
1-1/4" Pipe size
Gas meter
Based on Energy Content of 1,000 BTU/Cubic ft:
Divide each appliance's BTU requirement by 1,000 BTU/h to get the appliances Cubic Ft. requirement.
Take into account the distance the appliance is from the gas meter, look in the above gas chart to properly
size the line.
For sections of the gas line supplying gas to more than one appliance (Ex: Point A to Point B), add up the cubic
ft. requirements of the appliances that are being supplied by that section, and size to the farthest appliance.
For Example: The section from A to B supplies gas to the furnace, range and dryer. Adding up the BTU
requirements and dividing by 1,000 yields a cubic ft. requirement of 220 cubic ft. of gas. The farthest
appliance is the range, which is 50 ft. away from the meter. Looking at the above chart, and under the column
of 50 ft., Section A to B needs to be 1" in order to supply 220 cubic ft.
-Natural Gas Supply Piping-
30'
40'
50'
60'
200
171
152
138
377
323
286
259
775
663
588
532
880
798
Water
heater
199,000 BTU/h
10' Length
3/4" Pipe size
A
10' Length
1" Pipe size
5' Length
120,000 BTU/h
19
Length
70'
80'
90'
100'
127
118
111
104
239
222
208
197
490
456
428
404
734
683
641
605
35,000 BTU/h
15' Length
B
1" Pipe size
10' Length
3/4" Pipe size
Furnace
Range
65,000 BTU/h
Page
Installation Manual
Installation
Unit: Cubic feet per hour
125'
150'
200'
93
84
72
174
158
135
358
324
278
536
486
416
801
Dryer
10' Length
1/2" Pipe size
15' Length
1/2" Pipe size
C

Hide quick links:

Advertisement

Table of Contents
loading