Adjustment of the MIN and MAX value
The MIN and MAX value is the lowest respectively highest value that is allowed for the supply line
temperature. Adjusting the minimum and maximum supply line temperature is particularly important if
your home has floor heating. If your house has floor heating and parquet floor, the supply line
temperature should not be higher than 45°C. Else the floor might get damaged. If you have floor coils
and stone tiles, the MIN value should be 22-25°C in summer when no heating is required to obtain a
comfortable floor temperature.
MIN is the minimum setting of feed water temperature; it is adjustable by operator from10 to 30
factory setting is 22 ; if the room's floor use ceramic tile, then the setting of MIN can not less than
22
(this value can get a comfortable floor temperature); the heat pump will restart as soon as
actual feed water temperature less than MIN setting.
MAX is the maximum setting of feed water temperature, it is adjustable by operator from 30 to 70 ,
and factory setting is 70 ; if heat pump is using for floor heating, this setting is very important,
because at the time the feed water temperature can not higher than 70 , otherwise could be
dangerous; the heat pump will stop as soon as actual feed water temperature more than MAX
setting.
If there is a basement to your house, the MIN value should be adjusted to a suitable temperature in
summer too, to avoid a humid and chilly basement. In such cases, the value for HEAT STOP needs
being adjusted upwards. If you wish to change the MIN or MAX value:
1. Open the main menu INFORMATION by pressing the right- or left-hand button once. You will find the
cursor at the sub-menu OPERATION
2. Press the "down" button to move the cursor to the sub-menu HEAT CURVE
3. Open the selected menu by pressing the right-hand button once. You will find the cursor at the
parameter CURVE.
4. Press the "down" button to move the cursor to MIN.
5. Open the selected parameter by pressing the right-hand button once. The cursor is at MIN
6. Raise or lower the value, using the "up" and "down" button respectively.
7. Press the left-hand button three times to return to the main menu.
Repeat the procedure to change the MAX value, replacing MIN by MAX at step 4.

Adjustment of the HIGH T STOP and LOW T STOP value

'HIGH T STOP' and 'LOW T STOP' functions are only for room heating, the water tank
normally when the two functions are active.
The HIGH T STOP and LOW T STOP function stops water production to room floor when the outside air temperature
is equal to higher or lower than the value entered for HIGH T STOP or LOW T STOP. When the function is activated,
the circulation pump will be turned off. The factory setting of the HIGH T STOP is 50°C.( 0 ~ 50 °C adjustable )
The factory setting of the LOW T STOP is -50°C.( -50 ~ 0 °C adjustable )
If you wish to change the HIGH T STOP OR LOW T STOP value:
1
Open the main menu INFORMATION by pressing the right- or left-hand button once.
You will find the cursor at the sub-menu OPERATION
2
Press the "down" button to move the cursor to the sub-menu HEAT CURVE
3
Open the selected menu by pressing the right-hand button once.
4
You will find the cursor at the parameter CURVE.