Sub-Menu Heat Curve - OEM DC BWA-SS-7 Installation And Maintenance Instructions Manual

Dc inverter ground source heat pump - all in one
Table of Contents

Advertisement

ADD.HEAT
ON or OFF
ON select ON, electrical heater is running normally.
OFF select OFF, only switch off electrical heater the others are running normally.
If you wish to change operating mode:
a.
Open the main menu INFORMATION by pressing the right-hand button once. You will find the cursor at
the sub-menu named OPERATION.
b. Open the OPERATION menu by pressing the right-hand button once. You will find the cursor at the
previously selected operating mode.
c. Select the desired mode by pressing either the "up" or "down" button.
Return to the main menu by pressing the left-hand button twice.

Sub-Menu HEAT CURVE

This menu is used for making adjustments that affect the room temperature. For more information, please
refer to "Adjustments to be made regularly" on page 22.
Menu Text
CURVE
MIN
MAX
CURVE 5
CURVE 0
CURVE – 5
CURVE ROOM
HIGH T STOP
LOW T STOP
Description
The value entered shows the temperature of the water
to be distributed to the radiators (feed water
temperature) when the outside air temperature is 0°C.
Adjustment of value for lowest feed water temperature
allowed.
Adjustment of value for highest feed water
temperature allowed.
Adjustment of room temperature when the outside air
temperature is +5°C.
Adjustment of room temperature when the outside air
temperature is 0°C.
Adjustment of room temperature when the outside air
temperature is -5°C.
The translation of heat curve origin: change Room
value also can change Curve valve, in this way, the
Curve's slope is not change; if change the Curve
directly, its slope will change; to change every Room
value, the translation of Curve is1 .
When outdoor ambient temperature is higher than
this setting, the hot water to room or water tank will
be stopped
When outdoor ambient temperature is lower than
this setting, the hot water to room or water tank will
be stopped;
Control
Menus
Adjustable by
used(see "Adjustment
of CURVE value" on p22.)
used(see "Adjustment
of MIN & MAX value" on p26.
)
used(see "Adjustment
of MIN & MAX value" on p26.
)
used(see "Adjustment
of CURVE value" on p25.)
used(see "Adjustment
of CURVE value" on p25.)
used(see "Adjustment
of CURVE
value" on P25
used(see "Adjustment of
CURVE value" on p23.)
this setting is adjustable
from 0 to 50 ,factory
setting is 50 .
this setting is adjustable
from 0 to -50
, factory
setting is -50 .