ADD TIME ON
When choose mark " ", the Auto start function of electrical heater is active, choose "×"for cancel this function.
If this function is active, every day during the timing, the electrical heater will work normally.
ADD TIME OFF
When choose mark " ", the Auto stop function of electrical heater is active, choose "×"for cancel this function.
If this function is active, every day during the timing, the electrical heater will stop normally.
Sub-Menu SETTING
EMERGENCY1 (ON or OFF)
Emergency mode 1
mode, the unit will continuously execute the same objective (room heating only, water tank heating only,
or auto)
When select ON, compressor will be switch off, only electrical heater, water pump or other temperature
protection are available. When in water tank heating, the electrical heater will instead of compressor;
when in room heating mode, the electrical heater will runs depends on Integral; when in room heating
mode 1, the electrical heater will runs depends on Integral; when in room heating mode 2, the electrical
heater automatically starts, unless operator off the electrical heater.
EMERGENCY2(ON or OFF)
Emergency mode 2
mode, the unit will continuously execute the same objective (room heating only, water tank heating only,
or auto)
When select this mode, compressor will stop determined by outdoor ambient temperature, the
temperature setting is from 0 to -50 degree adjustable, factory setting is -25 degree, only electrical
heater, water pump or other temperature protection are available. When in water tank heating, the
electrical heater will instead of compressor; when in room heating mode, the electrical heater will runs
depends on Integral; when in room heating mode 1, the electrical heater will runs depends on Integral;
when in room heating mode 2, the electrical heater automatically starts, unless operator off the
electrical heater.
STERILIZE:
Sterilize water temperature: 60 --90
Sterilize duration : 10—90minutes default is10 minutes
Sterilize period : 7----99days default is 15 days
If the water tank's temperature always less than 60
pump will start the sterilize function ( the electrical heater start as soon as water get to 50 ), until
water temperature get to 60 (default) and last 10 minutes( default); or if 3 hours later the water
temperature still can not reach 60 , the sterilize function will exit.
ADD DIF TEMP
emergency 1
:
ON or OFF
emergency 2 : ON or OFF
adjustable default is 60
Control
Menus
factory setting is OFF(after select emergency
factory setting is OFF: (after select emergency
(default) and last 360 hours(period), the heat
28