Sub-Menu TEMPERATURE

This menu shows the different temperatures of the heating system. All temperature changes registered over
the last 60 minutes are stored in the control system and can be viewed in the shape of graphs.
LIQ U ID
RETURN AIR
OUT Display outdoor ambient temperature.
WARMWT
water tank temperature, the first value is water tank real temperature, the second value in
' ( )' is water tank setting temperature; the setting temperature is adjustable from 20
setting is 45 .(compressor restart must follow the program 'CMPDIF TEMP')
ROOM
Display room air temperature.
FEED 1.the first value is real feed water temperature, the second value in '( )' is feed water setting
temperature in ROOMHEAT MODE, it is adjusted by slope of Curve according to outdoor ambient
temperature. Factory setting is that feed water temperature is 40
0 , that is to say Curve is 40, the value of Curve is adjust from 22
available for Room heating, not for water tank heating.
2. under ROOMHEAT 1 mode, FEED setting can be adjust directly from 20 to 65 , factory setting
is 45 ; this setting is only available for room heating, not for water tank heating.
LIQ UID
Display Refrigerant temperature before evaporate.
RETURN AIR: Display Compressor return air temperature.
BR . IN:
Display the temperature of Brine system when entering the heat pump;it is adjustable from 15 to -12
factory setting is 0
BR. OUT: Display the temperature of Brine system when leaving the heat pump.
CMPDIF TEMP: compressor restart determined by water temperature degeneratiaon of water tank. This
setting is only for water tank heating, it is adjustable from 3 to 15
During heat pump's running, if the actual brine inlet temperature lowers than brine inlet setting water temperature,
heat pump stop running; during heat pump pause, the water pump will stop 5 minutes after it runs 1 minute, this
is for absorb the heat for brine water and update brine water temperature information; heat pump will restore
running when actual brine inlet temperature higher than setting temperature 2.5
When at item WARMWT or RETURN or FEED, or BRINE IN or BRINE OUT, press button Right
5 seconds willdisplay the information as follow kind of chart, to check how the temperature is going
in one hour.

Sub-Menu INTEGRAL

Control
Menus
RETURN
.
Display real return water temperature.
when outdoor ambient temperature is
to 56 . This setting is only
, and factory setting is 5 .
.
to 62 , factory
,