Sub-Menu RESET

Reset to factory setting value.

Sub-Menu MAN TEST

How to enter the Sub-Menu MAN TEST:
You need to choose the " MAN TEST" on the main menu ( INFORMATION) And press the right button for 3
second .
Man test for installation
On sub-menu OPERATION---MAN TEST
ADD1 / 2 / 3
ON or OFF
3 WAY
ON or OFF
4 WAY
ON or OFF
WARM PUMP
ON or OFF
BRINE PUMP
ON or OFF
CMP
ON or OFF
CMP B
ON or OFF
P.S : the compressor only runs 5 minutes for testing, at that time its frequency is 45Hz.
This menu is for installation engineer, user operation is prohibitive. The testing function will dissolve as
soon as the menu is off the interface.
Control
Menus
B
ADD1 / 2 / 3 ( electrical heater 1 / 2 /3 )
3-WAY VALVE
4-WAY VALVE
WATER PUMP
BRINE PUMP
COMPRESSOR
COMPRESSOR B ( invalid )