System Settings - Nibe F1245 Installer Manual

Ground source
Hide thumbs Also See for F1245:
Table of Contents

Advertisement

7 System settings

Make different system settings for the heat pump here,
e.g. which accessories are installed.
There are two ways of activating connected accessories.
You can either mark the alternative in the list or use the
automatic function "search installed acc.".
search installed acc.
Mark "search installed acc." and press the OK button to
automatically find connected accessories for F1245.
Caution
"level sensor" are not found automatically but
must be ticked off by hand.
NOTE
Only mark the option for ground water pump
if the accessory AXC 40 is to be used to control
the circulation pump.
NIBE™ F1245
8 Room sensor settings
factor system
Setting range: 0.2 - 3.0
Default value: 2.0
Room sensors to control the room temperature can be
activated here.
Here you can set a factor that determines how much the
supply temperature is to be affected by the difference
between the desired room temperature and the actual
room temperature. A higher value gives a greater change
of the heat curve offset.
If several climate systems are installed the above settings
can be made for the relevant systems.
Chapter 6 |
Commissioning and adjusting
31