Installation Examples; Fully Dedicated System - Fantech SHR Series Installation Manual

Shr/vhr series heat recovery ventilators
Table of Contents

Advertisement

Available languages

Available languages

Installation examples

Example only – duct configuration may differ depending on the model.

FULLy DEDICATED SySTEM

BEST FOR NEw CONSTRUCTION
Stale air is drawn from key areas of home (bathroom, kitchen, laundry)
Fresh air supplied to main living areas
1. Furnace blower must operate when ventilation from HRV is required. The
furnace should be set to run continuously or interlocked with HRV.
2. Weatherhood arrangement is for illustrative purposes only. 3m (10')
minimum separation and 460 mm (18") above grade is recommended.
3. Due to the differences in pressure between the HRV and the equipment it is
being connected to, the HRV's airflow must be balanced on site, using the
procedure found in section "AIRFLOW BALANCING".
Bedrooms
Fresh Air
Exhaust Air
Suggested installation for:
• Hydronic baseboard
• Infloor heating
• Electric baseboard
• Mini split heat pump
Benefits: Provides the best
fresh air distribution in the
house; lowest operation cost
since the furnace/air handler
unit is not needed.
FEL 4 (4" Miter Elbow)
Exhaust CG 4 (4" Adjustable Grill)
Bathroom
Central Control - optional
Fresh air to living room
HRV
460 mm
5
fantech