Note Warning/ Information Technical Practical tip Important information note PLEASE READ AND SAVE THESE INSTRUCTIONS For residential use only Before installation careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler operating at a higher static pressure.
DETERMINING YOUR AIRFLOW REQUIREMENT Room Count Method Room classification Number of rooms CFM (L/s) CFM Required Master bedroom x 10 L/s (20 CFM) if yes add 10 L/s (20 CFM) Basement yes or no if no = 0 Bedrooms x 5 L/s (10 CFM) Living room x 5 L/s (10 CFM) Others...
INSTALLATION EXAMPLES Suggested installation for: Example only – duct configuration may differ depending on the model. • Hydronic baseboard • Infloor heating FULLY DEDICATED SYSTEM • Electric baseboard BEST FOR NEW CONSTRUCTION • Mini split heat pump Benefits: Provides the best Stale air is drawn from key areas of the home requiring local exhaust fresh air distribution in the (bathroom, kitchen, laundry room).
Figure 1 return air duct that closes when the ERV is not operating. See wiring diagram (figure 1). You may also choose to use a Fantech ERV that uses a recirculation defrost that incorpo- *Transformer and Damper motor not included...
Figure 1 return air duct that closes when the ERV is not operating. See wiring diagram (figure 1). You may also choose to use a Fantech ERV that uses a recirculation defrost that incorpo- *Transformer and Damper motor not included...
EXTERIOR DUCTING INSTALLATION WEATHERHOOD LOCATION OUTSIDE CORNER INSIDE CORNER • Decide where your intake and exhaust hoods will be located. 36" (1m) 36” (1m) Locating the Intake Weatherhood • Should be located upstream (if there are prevailing winds) from the 3' (900mm) exhaust outlet.
INTERIOR DUCTING INSTALLATION • To maximize airflow through the ductwork system, all ducts should be kept short and have as few bends or elbows as possible. • 45º elbows are preferable to 90º. • Use “Y“ ducts instead of “T” ducts whenever possible. •...
ERV INSTALLATION LOCATION The ERV must be located in a conditioned space where it will be possible to conveniently service the unit. Typically the ERV would be located in the mechanical room or an area close to the outside wall where the weatherhoods will be mounted.
INSTALLING DRAIN LINE Through normal operation and during its defrost mode, the ERV may produce some condensation. This water should flow into a nearby drain, or be taken away by a condensate pump. The ERV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point. A “P”...
Page 12
Airflow balancing (Cont'd) Adjusting airflows A damper is integrated into the Fresh Air to Building collar and on to the Stale Air to Outside. This damper replaces the installation of a separate damper into the Fresh Air to Building and on to the Stale Air to Outside ducting line.
Low Voltage Control Systems * Please see instruction manuals for individual controls for proper wiring and set up of control systems. CENTRAL CONTROLS These control options can only be used individually Ensure that unit is not CONTROLS FEATURES CONNECT TO plugged when connecting ECO-Touch®...
Page 15
WIRING DIAGRAM (CONT'D) WIRING DIAGRAM TO Standard Accessory Control Contact Standard Furnace Interlock Wiring FURNACE THERMOSTAT TERMINALS FOUR WIRE TWO WIRE heating only FOR A FURNACE CONNECTION TO A COOLING SYSTEM: On some newer furnaces and older FURNACE thermostats, energizing the R and 24-VOLT TERMINAL BLOCK G terminal at the furnace has the...
TROUBLESHOOTING Problem Causes Solutions Air is too dry Dehumidistat control is set too low Increase the desired level of humidity. Change ventilation mode from continuous mode to standby. ERV out of balance Have contractor balance ERV airflows Air is too humid Dehumidistat control is set too high Reduce the desired level of humidity.
Lines beginning of the warranty period. Vacuum the Inside of the Annually • The fans found in all Fantech ERVs Unit require no lubrication, and are factory balanced to prevent vibration and Clean and Un-block Annually promote silent operation.
ERV core washing instructions For proper maintenance of your energy recovery core please follow these instructions Remove both filters by sliding them out. Remove the core from the unit. With one of your core's air inlets facing down, place it in a large sink, bathtub, or shower.