IMPORTANT - PLEASE READ THIS MANUAL
BEFORE INSTALLING UNIT
CAUTION -
Before installation, careful consideration must be given to how this system
will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace
or air handler, operating at a higher static. After installation, the compatibility of the two pieces
of equipment must be confirmed by measuring the airflow's of the Energy Recovery Ventilators
by using the balancing procedure found in this manual.It is always important to assess how
the operation of any ERV may interact with vented combustion equipment (i.e. Gas Furnaces,
Oil Furnaces, Wood Stoves, etc.).
NEVER -
install a ventilator in a situation where its normal operation, lack of operation or
partial failure may result in the backdrafting or improper functioning of vented combustion
equipment!!!
Your ventilation system should be installed in conformance with the appropriate state requirements or in the
absence of such requirements ASHRAE's " Good Engineering Practices".
SER 1504, SER 1504N, SER 2004, SER 2004N, SER 3204D & SER 3204N
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
SER Models
SER Series
Energy Recovery Ventilator
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SER 1504N and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Fantech SER 1504N

  • Page 1 Your ventilation system should be installed in conformance with the appropriate state requirements or in the absence of such requirements ASHRAE’s “ Good Engineering Practices”. SER Models SER 1504, SER 1504N, SER 2004, SER 2004N, SER 3204D & SER 3204N INSTALLATION, OPERATION AND MAINTENANCE MANUAL...
  • Page 2: Table Of Contents

    SER 1504N ........
  • Page 3: Ser 1504

    Electrical box, placed on the outside of the unit, can also be easily accessed. Distributed by: Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ fea- tures, designs, components and specifications to maintain their technological leadership position.
  • Page 4 Project #: 1712 Northgate Blvd. 50 Kanalflakt Way Location: Sarasota, FL. 34234 Bouctouche, NB E4S 3M5 Phone: 800.747.1762; 941.309.6000 Phone: 800.565.3548; 506.743.9500 Architect: Fax: 800.487.9915; 941.309.6099 Fax: 877.747.8116; 506.743.9600 Engineer: www.fantech.net www.fantech.ca Contractor: info@fantech.net info@fantech.ca Article #: 301XXX Rev Date: 110104...
  • Page 5: Ser 1504N

    23˚F (-5˚C) for more than 2 consecutive days. Distributed by: Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ fea- tures, designs, components and specifications to maintain their technological leadership position.
  • Page 6 0.56 0.55 Total Recovery Efficiency Cooling Specifications and Ratings • Model: SER 1504N • Insulated with 1" (25 mm) high density • Supply & exhaust ducts: 6" (152.4mm) • Total assembled weight: 45 lbs polystyrene foam to prevent condensation • Mounting: Suspended by chains & hooks •...
  • Page 7: Ser 2004

    Electrical box, placed on the outside of the unit, can also be easily accessed. Distributed by: Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ fea- tures, designs, components and specifications to maintain their technological leadership position.
  • Page 8 Project #: 1712 Northgate Blvd. 50 Kanalflakt Way Location: Sarasota, FL. 34234 Bouctouche, NB E4S 3M5 Architect: Phone: 800.747.1762; 941.309.6000 Phone: 800.565.3548; 506.743.9500 Fax: 800.487.9915; 941.309.6099 Fax: 877.747.8116; 506.743.9600 Engineer: www.fantech.net www.fantech.ca Contractor: info@fantech.net info@fantech.ca Article #: 301XXX Rev Date: 110104...
  • Page 9: Ser 2004N

    23˚F (-5˚C) for more than 2 consecutive days. Distributed by: Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ fea- tures, designs, components and specifications to maintain their technological leadership position.
  • Page 10 Project #: 1712 Northgate Blvd. 50 Kanalflakt Way Location: Sarasota, FL. 34234 Bouctouche, NB E4S 3M5 Architect: Phone: 800.747.1762; 941.309.6000 Phone: 800.565.3548; 506.743.9500 Fax: 800.487.9915; 941.309.6099 Fax: 877.747.8116; 506.743.9600 Engineer: www.fantech.net www.fantech.ca Contractor: info@fantech.net info@fantech.ca Article #: 301XXX Rev Date: 110104...
  • Page 11: Ser 3204D

    Distributed by: outside of the unit, can also be easily accessed. Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ fea- tures, designs, components and specifications to maintain their technological leadership position.
  • Page 12 Project #: 1712 Northgate Blvd. 50 Kanalflakt Way Location: Sarasota, FL. 34234 Bouctouche, NB E4S 3M5 Architect: Phone: 800.747.1762; 941.309.6000 Phone: 800.565.3548; 506.743.9500 Fax: 800.487.9915; 941.309.6099 Fax: 877.747.8116; 506.743.9600 Engineer: www.fantech.net www.fantech.ca Contractor: info@fantech.net info@fantech.ca Article #: 301XXX Rev Date: 110104...
  • Page 13: Ser 3204N

    23˚F (-5˚C) for more than 2 consecutive days. Distributed by: Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ fea- tures, designs, components and specifications to maintain their technological leadership position.
  • Page 14 Project #: 1712 Northgate Blvd. 50 Kanalflakt Way Location: Sarasota, FL. 34234 Bouctouche, NB E4S 3M5 Architect: Phone: 800.747.1762; 941.309.6000 Phone: 800.565.3548; 506.743.9500 Fax: 800.487.9915; 941.309.6099 Fax: 877.747.8116; 506.743.9600 Engineer: www.fantech.net www.fantech.ca Contractor: info@fantech.net info@fantech.ca Article #: 301XXX Rev Date: 110104...
  • Page 15: Operation

    The entire line of SER series Energy Recovery Ventilators comes equipped with Fantech's new electronic uni-control board which offers a wide vari- ety of features making it the ultimate ventilation control system. Fantech engineers have used the latest technology to provide solid, trouble free oper- ation under any conditions.
  • Page 16: Optional Remote Controls

    4 1/2" side of the ERV will be Control multiple func- (114 mm) automatically deactivated tions of your Fantech OVERRIDE TIMER giving the user complete ERV with one slimline When pressed, unit control from wherever wall control.
  • Page 17: Intellitek Multi-Function Controls Edf2

    To Control multiple functions of move from one time to the your Fantech SER with one other, continue pressing the slimline wall control. Two wire timer button until you reach connection simplifies installa- the desired time.
  • Page 18: Installation

    INSTALLATION LOCATION PRACTICAL TIPS The ERV should be located in a conditioned space where it will be possible to conveniently service the unit. Typically the ERV would be located in the mechanical room or an area close to the out- side wall where the weatherhoods will be mounted.
  • Page 19: Location & Ducting

    INSTALLING DUCTS GOING TO / FROM OUTSIDE A well designed and installed ducting system will allow the ERV to operate at its maximum efficiency. PRACTICAL Always try to keep duct runs as short and straight as possible. See Installation Diagrams for installation examples. TIPS INSTALLING THE DUCTING •...
  • Page 20 In homes without a forced air furnace, fresh air should be supplied to all habitable rooms including, bedrooms and living areas. It should be supplied from high wall or ceiling locations. Grills that diffuse the air comfortably such as Fantech grille {MGE (metal) or PGE (plastic)}s are recommended.To avoid possible noise transfer through the ductwork system, a short length (approximately 12”,...
  • Page 21 • For proper network of ducting, see TYPES OF INSTALLATIONS. 4 Push the Fantech grill - MGE (metal) or PGE (plastic) - into the optional • The Grills are to be mounting collar or directly into installed elbow. installed on the ceiling or on the wall 6”...
  • Page 22: Examples

    INSTALLATION EXAMPLES It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended. All air movement devices have a performance curve. The amount of air (CFM) that an ERV will deliver is directly related to the total external static pressure (E.S.P.) of the system.
  • Page 23: Installation Examples

    INSTALLATION EXAMPLES (CONT'D) Example diagram only-duct configuration may change depending on model DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN (Stale air drawn from key areas of home) Exhaust Partially Dedicated System Central Control - optional Bathroom Bedrooms Return Air...
  • Page 24 INSTALLATION EXAMPLES (CONT'D) Example diagram only-duct configuration may change depending on model DIRECT CONNECTION of both the ERV SUPPLY AIR STREAM and EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN Simplified Installation Option 1 (Return/Return Method) • ERV must be balanced •...
  • Page 25 INSTALLATION EXAMPLES (CONT'D) Example diagram only-duct configuration may change depending on model DIRECT CONNECTION of both the ERV SUPPLY AIR STREAM & EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN & SUPPLY AIR SIDE Simplified Installation Option 2 (Supply/Return Method) •...
  • Page 26: Air Flow Balancing

    AIR FLOW BALANCING CAUTION • If the unit’s airflows are not properly balanced... - The unit may not operate at it’s maximum efficiency. - Energy recovery core damage may occur. - The unit’s use could cause negative or positive pressure in your home causing cold air to enter or other combustible equipment to backdraft.
  • Page 27: Maintenance

    AIR FLOW BALANCING (CONT'D) AIRFLOW STATION (GRID) METHOD 1 For this flow measuring station, cut 3 Adjust the damper until you reach the desired velocity. the duct and place the flow (damper should be 18” from grid) measuring station between each station.
  • Page 28: Troubleshooting

    TROUBLESHOOTING Problem Causes Solutions Air is too dry Dehumidistat control is set too low Increase the desired level of humidity. Change ventilation mode from continuous mode to standby. ERV out of balance Balance ERV Reduce the desired level of humidity. Combine this step with use of con- Air is too humid Dehumidistat control is set too high tinuous exchange mode.
  • Page 29: Electrical Connections

    ELECTRICAL CONNECTIONS 3 position mode Found on Accessory Control Contact selection switch (Open & Closes contact when HRV/ERV is ON/OFF) electrical Diagnostic Dehumidistat Mechanical Dehumidistat 2 wires Crank Timer On/Off 2 wires 4 wires Custom defrost mode jumper selection and / and / (1 only) EDF5 or EDF2...
  • Page 30: Wiring Diagrams

    ELECTRICAL WIRING DIAGRAMS SER 1504, SER 1504N, SER 2004 & SER 2004N...
  • Page 31 ELECTRICAL WIRING DIAGRAMS SER 3204D SER 3204N...
  • Page 32 Fax: 877.747.8116; 506.743.9600 www.fantech.net; info@fantech.net www.fantech.ca; info@fantech.ca Fantech, reserves the right to modify, at any time and without notice, any or all of its products’ features, designs, Article #: 301096 Item #: 401455 components and specifications to maintain their technological leadership position.