Autronica Autroprime Connecting

Autronica Autroprime Connecting

Interactive fire detection systems
Hide thumbs Also See for Autroprime:

Advertisement

Interactive Fire Detection Systems
Connecting Loop Units
Protecting life, environment and property...
116-P-CONNECTLOOPUNIT/DGB 2007-10-10

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Autroprime and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Autronica Autroprime

  • Page 1 Interactive Fire Detection Systems Connecting Loop Units Protecting life, environment and property... 116-P-CONNECTLOOPUNIT/DGB 2007-10-10...
  • Page 2 This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose. Autronica Fire and Security AS and its subsidaries assume no responsibility for any errors that may appear in the publication, or for damages arising from the information in it.
  • Page 3: Table Of Contents

    3.22 Day/Night Control Unit with Timer Input (BW-203) ......30 3.23 Remote Alarm Control Unit (BU-200) ..........31 3.24 Interface Unit for Conventional Loops (BN-330) ....... 32 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 1...
  • Page 4 Table of Contents 4. Reader’s Comments ............33 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 2...
  • Page 5: Introduction

    1. Introduction 1.1 About the Handbook This document provides information on how to connect detectors and other loop units to the Interactive Fire Detection Systems Autroprime and AutroSafe. Note that some loop units can be connected to AutroSafe only (the indication “AutroSafe only”...
  • Page 6: Connections To Detectors

    Input Output 1 - IN 2 - OUT 3 + COMMON 4 - LED 2.2 LED Connection on Detector Varistor SIOV-S07K25 Input Output BU-46 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 4...
  • Page 7: Connection Of Branch-Off

    1 - IN 2 (-) and 3 (+). 2 - OUT Input 3 + COMMON 4 - LED Output Branch-off Next detector on branch-off Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 5...
  • Page 8: Detector Head / Base Alignment

    O P T IC A L D E TE C TO R BH H 3 20 001 1998 239 0001 001 1998 239 0001 EN 54 /7 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 6...
  • Page 9: Detector Locking Mechanism

    The new springloaded tongue (figure 3) on the detector head will lock the head in a correct position if the locking nub has been removed before mounting. Springloaded tongue Detector head with springloaded tongue Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 7...
  • Page 10: Removing A Locked Detector Head

    (for example a paper clip or similar) to push the springloaded tongue in, and simply turn the detector head counter-clockwise. Use this hole to access and release the locking mechanism. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 8...
  • Page 11: Detector Dust Covers

    Connections to Detectors 2.7 Detector Dust Covers Autronica detectors are supplied with a dust cover. To avoid possible contamination of the detector chamber during installation, these should remain in place on the detector until commissioning is started. IMPORTANT: LEAVE DETECTOR DUST...
  • Page 12: Connections To Other Loop Units

    The following subsections show the connection of various Loop Units. For more detailed information on the Loop Units described in this chapter, please refer to data sheets and other relevant user documentation from Autronica Fire and Security AS. 3.2 Manual Call Points I/O Unit...
  • Page 13: Autrosense Micra 25 High Sensitivity Aspirating Detector

    N o . 24 V DC 24 V DC AutroSense Micra 25 AutroSense Micra 25 AutroSense Micra 25 BN-300 2 3 4 Detection Detection loop loop Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 11...
  • Page 14: Autrosense Micra 100 High Sensitivity Aspirating Detector

    N o . 24 V DC 24 V DC AutroSense Micra 100 AutroSense Micra 100 AutroSense Micra 100 BN-300 2 3 4 Detection Detection loop loop Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 12...
  • Page 15: Autrosense 75 Aspirating Smoke Detector

    + 24 V DC (to next detector) Connection to 24V DC 24V DC in 24V DC out Loop + 24 V DC + 24 V DC Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 13...
  • Page 16: Autrosense 200 High Sensitivity Aspirating Detector

    Prewarn. contact N.O. AutroSense 100 AutroSense 200 Input A Input B standard interfaceboard standard interfaceboard NC NO 11 10 BNA-320 Main loop out Main loop in Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 14...
  • Page 17: Autroflame X33Af Multispectrum Infrared Flame Detector

    N r. N o. N o. N o. Alarm Alarm Alarm signal signal signal Power Power Power AutroFlame X33/1 AutroFlame X33/1 AutroFlame X33/1 AutroFlame X33AF Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 15...
  • Page 18: Autrobeam 100 Infrared Beamdetector System

    24 VDC Module Alarm signal AutroBeam 100 AutroBeam 100 AutroBeam 100 AutroBeam 100 AutroBeam 100 Receiver Transmitter Fire Alarm Control Panel Power (Drawing No. bs-1160) Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 16...
  • Page 19: Autrobeam 25 Infrared Beamdetector

    Interface unit Alarm signal Reflector AutroBeam 25 AutroBeam 25 24VDC ALARM RELAY FAULT RELAY NC NO 11 10 BN-320 Main loop in Main loop out Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 17...
  • Page 20: Programmable Electronic Sounders (Bbr-200)

    P RE S S H ER E B R EAK G LASS Loop Driver Module Electronic Sounder w/address/interface board BBR-200 Detection loop out Detection loop in Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 18...
  • Page 21: Addressable Socket Sounder (Bbr-110)

    Terminal connection 1 - Out: Terminal connection - out on circuit board Common (+ In and + Out): Terminal connection 3 External LED: Terminal connection 4 Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 19...
  • Page 22: Ex Ia-Approved Detectors

    NON EX TERMINALS Safe Area BARRIER DIN RAIL P&F 1.54 BZB-500 EX TERMINALS Ex-Area Ex-Branch for Ex ia-approved Detectors Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 20...
  • Page 23: Disable Input With Pushbuttons (Bw-200)

    Separate 24V DC must always be used when if more than 2 units are connected to the loop, or if the 24V output is used. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 21...
  • Page 24: Door Control Unit (Bn-320/2)

    Switch 1 Closed Open Open Closed Switch 2 Open Open Closed Closed Status Door Door in Door Closed Illegal Open transition (fault) Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 22...
  • Page 25: Monitoring And Control Unit (Bn-320/4)

    BREAK GLASS Loop Driver BN - 320/4 Module BN - 320 BRANNALAR Tilpasningsenhet FIRE ALARM Interface unit Output Input A Input B External Equipment External Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 23...
  • Page 26: Sprinkler Control Unit (Bn-320/5)

    Tilpasningsenhet Tilpasningsenhet FIRE ALARM FIRE ALARM FIRE ALARM Interface unit Interface unit Interface unit Sprinkler Sprinkler Input A Input A Flow Flow Switch Switch Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 24...
  • Page 27: Monitoring Input Unit (Bn-201)

    C lass 4 circuit. • Class 4: Normal N .C . 2KO hm Closed contact without ‘activate’ resistor, fault monitored for short circuit. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 25...
  • Page 28: Input Unit With Selfverify (Bn-300)

    N o . 1. Pos (+) in 2. Pos (+) out 3. Neg (-) in 4. Neg (-) out 5. (-) Input BNB-300/32 6. (+) Input Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 26...
  • Page 29: Single Relay Output Unit (Bn-310)

    7. N.A 3. Neg (-) in 8. N.A 4. Neg (-) out 9. Normally open Relay 10. Normally closed contact 11. Common Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 27...
  • Page 30: Day/Night Control Unit With Pushbuttons (Bw-202)

    Separate 24V DC must always be used when if more than 2 units are connected to the loop, or if the 24V output is used. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 28...
  • Page 31: Disable Input With Timer Input (Bw-201)

    Separate 24V DC must always be used when if more than 2 units are connected to the loop, or if the 24V output is used. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 29...
  • Page 32: Day/Night Control Unit With Timer Input (Bw-203)

    Separate 24V DC must always be used when if more than 2 units are connected to the loop, or if the 24V output is used. Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 30...
  • Page 33: Remote Alarm Control Unit (Bu-200)

    G LA S S G LA S S Interface unit Interface unit Interface unit Loop Loop Driver Driver 24VDC 24VDC BW-200 BW-200 BU-200 Module Module Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 31...
  • Page 34: Interface Unit For Conventional Loops (Bn-330)

    - AL_Com in + AL-Com out - AL_Com out + 24V Input Conventional loop 15V/24V select T-output / Open collector + conventional loop - conventional loop Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS Page 32...
  • Page 35 Title: Connecting Loop Units, Interactive Fire Detection Systems, Ref. No.: 116-P-CONNECTLOOPUNIT/DGB 2007-10-10 Your information on any inaccuracies or omissions (with page reference): Please turn the page Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS...
  • Page 36 ------------------------------------------------------------------------------------------------ Fax: ------------------------------------------------------------------------------------------------ Date: ------------------------------------------------------------------------------------------------ Please send this form to: Autronica Fire and Security AS N-7483 Trondheim Norway Tel: + 47 73 58 25 00 Fax: + 47 73 58 25 01 www.autronicafire.com Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10,...
  • Page 37 Reader’s Comments Connecting Loop Units, Interactive Fire Detection Systems, 116-P-CONNECTLOOPUNIT/DGB 2007-10-10, Autronica Fire and Security AS...
  • Page 38 Autronica Fire and Security is an international company, headquartered in Trondheim, one of the largest cities in Norway. The company is owned by United Technologies Corporation and employs more than 319 persons with experience in developing, manufacturing and marketing of fire safety equipment. Our products cover a broad range of systems for integrated solutions, including fire detection systems, integrated fire and gas detection systems, control and presentation systems, voice alarm systems, public address systems, emergency light systems, plus suppression systems.

This manual is also suitable for: