Autronica AutroSafe Installation Handbook

Autronica AutroSafe Installation Handbook

Interactive fire detection system
Hide thumbs Also See for AutroSafe:
Table of Contents

Advertisement

Release 4
Installation Handbook
AutroSafe Interactive Fire Detection System
116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire And Security AS

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AutroSafe and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Autronica AutroSafe

  • Page 1 Release 4 Installation Handbook AutroSafe Interactive Fire Detection System 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire And Security AS...
  • Page 2 This product should not be mixed with other commercial wastes for disposal. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security...
  • Page 3: Table Of Contents

    6.10 Cut Out Dimensions for Flush Mounting in a Wall ......30 6.10.1 Repeater Panel BU-BV-420 ............ 30 6.10.2 Operator Panel BS-430 ............31 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 3...
  • Page 4 10.10.3 Power Connection Overview ..........49 10.11 Mains Power Connections..............50 10.11.1 Power Cabinet STX .............. 50 10.11.2 Power Supply BPS-410 ............50 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 4...
  • Page 5 15.12.1 Ribbon Cable Connector BSA-400 to Terminal Block L1 ..71 15.12.2 Switch Setting – Switch S6 and S1 ........71 15.13 RS-422 Connections ................. 72 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 5...
  • Page 6 18.1 Mounting Power Cabinet BP-405 (obsolete) ........88 18.2 Power Cabinet and Power Units ............91 18.2.1 Power Cabinet BP-405 (OBSOLETE)........91 18.2.2 Power Unit BPS-405 (OBSOLETE) ........91 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 6...
  • Page 7: Introduction

    Controller Boards with BSA-400A Controller Boards, refer to separate handbook. 1.3 The Reader The handbook is intended to be used by Autronica Fire and Security trained service and technical personnel who are responsible for the installation of the AutroSafe Interactive Fire Detection System, Release All tasks described in the handbook are to be performed without applying power to the system.
  • Page 8: Reference Documentation

    Datasheet; Power Unit BPS-405 (obsolete) Datasheet; Power Unit BPS-410 Datasheet; AutroKeeper BN-180 NOTE: Autronica Fire and Security provides documentation in other languages and will be continuously updated according to changes in the English version. All documents can be downloaded at http://product.autronicafire.com/products/...
  • Page 9: Safety

    PERIODIC TESTING OF THE SYSTEM IN ACCORANCE WITH THE INSTRUCTIONS PROVIDED IN THE USER MANUAL IS THE ONLY WAY TO ENSURE ALL SENSORS, DETECTORS AND PANEL ACCESSORIES ARE FUNCTIONING PROPERLY. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 9...
  • Page 10: National Standards And Regulations

    PROPERLY IN ALL ENVIRONMENTS AND APPLICATIONS. 2.2 National Standards and Regulations Products from Autronica Fire and Security are developed and manufactured in compliance with international safety standards. Any additional national or local safety standards that apply where the equipment is installed and operated, must also be taken into account together with the safety regulations in the product documentation.
  • Page 11: System Design, Installation, Commissioning, Testing And Validation

    Modifications to the products mentioned in this handbook shall not be carried out. If a fault or malfunction occurs, the product in question shall be replaced with a new one. Contact your local Autronica contact or dealer for further information.
  • Page 12: Safety Notices

    2.8.1 Standards NFPA 70 and NFPA 72 To meet UL 864 installation requirements, the AutroSafe installation must be in accordance with the following standards: • National Electrical Code, NFPA 70 •...
  • Page 13: Environment Compatibility

    This product should not be mixed with other commercial wastes for disposal. Make sure to comply with all local and currently applicable laws and regulations. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 13...
  • Page 14: Pre-Installation

    175 cm above the floor. Other panels should be mounted accordingly. 175 cm cm cm asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 14...
  • Page 15: System Units - Overview

    The Information Panel serves as an indication device only. It provides information related to the defined operation zone(s). Dimensions: HxWxD (mm): 195 x 350 x 84 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 15...
  • Page 16 12V/65Ah batteries (not included). Power supply failures that may occur must be reported to the AutroSafe panel. In order to report such failures, an additional input module is required. Other input modules can be used for this purpose, for example, BN-303, BN-304 or BN-305.
  • Page 17: Power Supplies

    In general, the type of power supply must be selected according to project specifications. Note: If BSD-330 (interface between the AutroSafe detector loop protocol and BS-100 loop protocol) is to be used, the BPS-410 Power Unit must be used. Refer to chapter 6.6 and chapter 6.7 for details on mounting.
  • Page 18: Loop Panels - Overview

    HxWxD (mm): 154 x 310 x 45 Fire Brigade Loop Panel (BU-110) Mounted onto a wall bracket (UD-732). Dimensions (mm): HxWxD (mm): 154 x 310 x 45 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 18...
  • Page 19: Mounting Instructions

    For information on mounting the Controller Rack BC-440, refer to separate datasheet. This product contains static-sensitive devices. Always use an antistatic wrist strap / earth bracelet to avoid any electrostatic discharge. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 19...
  • Page 20: Mounting Fire Alarm Control Panel Bs-420/Controller Bc-420

    The cabinet has 3 ◼ mounting holes holes according to the located at the illustration. rear. The 2 upper holes are of key- hole-type. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 20...
  • Page 21 Insert the text foils (in For detailed ◼ description of the the appropriate various text foils, language) into their see chapter 6.8. respective positions. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 21...
  • Page 22: Mounting The Operator Panel Bs-430

    10. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 22...
  • Page 23: Mounting Repeater Panel Bu-Bv-420

    The cabinet has 5 holes. mounting holes located at the rear. The upper 3 holes are of key- hole-type. Partly fasten the upper ◼ screws. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 23...
  • Page 24 Insert the text foils (in ◼ description of the the appropriate various text foils, language) into the their see chapter 6.8. respective positions. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 24...
  • Page 25: Mounting Loop Panels (Bv-110 And Bu-110)

    AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 25...
  • Page 26: Mounting Power Cabinet Stx Range

    Mounting Instructions 6.6 Mounting Power Cabinet STX Range AutroSafe Release 4 provides Power Cabinet STX Range. The power cabinet is available in three different versions, including either a 2A, 5A or 10A power supply. All versions have space for two 12V/18Ah batteries (not included).
  • Page 27: Mounting Power Supply Unit Bps-410

    Power Unit BPS-410 (including a 24V/10A power supply), a calibration procedure must be performed. Refer to the Commissioning Handbook, Calibration Procedure – Power Unit BPS-410. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 27...
  • Page 28: Inserting Text Foils

    (along the perforation holes). Fire Alarm Control Panel BS-420 is shown in the example below. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 28...
  • Page 29: Cable Inlets / Outlets

    ø23 x 6 The illustration above shows the positioning and dimensions of the cable inlets for BS-420/BC-420 (the uppermost illustration) and BU-BV-420. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 29...
  • Page 30: Cut Out Dimensions For Flush Mounting In A Wall

    6.10.1 Repeater Panel BU-BV-420 The illustration below shows the cabinet’s cut out dimensions. The dimensions given include space for the cover frame. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 30...
  • Page 31: Operator Panel Bs-430

    6.10.2 Operator Panel BS-430 The illustration below shows the cabinet’s cut out dimensions. The dimensions given include space for the cover frame. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 31...
  • Page 32: Power Consumption

    7.1 Mains Power 7.1.1 STX Power Refer to datasheet for Power Cabinet STX and the documentation for each variant (2A, 5A and 10A) found on the Autronica Product Web (see links in this handbook, chapter 6.6). 7.1.2 BPS-410 The current consumption at 115V AC is 4,5A.
  • Page 33: Phoenix Ethernet Switches

    AutroNet Ring Topology is used (refer to chapter 10.6.3). Only Phoenix Ethernet switches are approved and supported by Autronica Fire and Security AS. The switch type and the number of switches depend on the actual installation / network design (number of panels and the transmission length between the panels / switches).
  • Page 34: Cable Connection Overview

    A1+/- and J18/1 / J18/ 2). AFB Earth Fault Sense Power Supply Power Cabinet BPS-410 BP-405 Power Board BSF-400 Batt 1 2 3 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 34...
  • Page 35: Connecting Internal Cables

    Connecting Internal Cables 9. Connecting Internal Cables 9.1 Overview – BS-420 / BC-420 Multifunction cable XGE-1/20-40 AL_Com+ cable XGE-1/10-50 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 35...
  • Page 36: Bs-420 / Bc-420

    A ribbon cable is connected between the Multifunction Serial Port Connector and the main terminal block (mounted on the DIN rail inside the cabinet). Connector J3 Multifunction cable XGE-1/20-40 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 36...
  • Page 37: Multifunction Serial Port Connection On Terminal Block, List L1

    Multifunction Serial Port Reference J3.16 L1.17 Fault Relay Normal Open J3.17 L1.18 J3.18 L1.19 Fault Relay Normal Closed J3.19 L1.20 Fault Relay Common J3.20 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 37...
  • Page 38: Internal Earth Cabling

    Connecting Internal Cables 9.3 BC-440 For information on the cabling to AutroSafe Controller Rack BC-440, refer to separate datasheet. 9.4 Internal Earth Cabling asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 38...
  • Page 39: Connecting External Cables

    The isolation of the mains wiring must be of either: • inflammability class V2 or • the wiring has to be fixed to the cabinet separated from all other cables asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 39...
  • Page 40: 115/230Vac Voltage Bps-410

    L1.13 L1.15 Terminal block L1 with unshielded AutroFieldBus cable L1.3 Last AFB unit L1.5 L1.7 L1.9 First AFB unit L1.11 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, L1.13 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 40 L1.15...
  • Page 41: Connections To Connector J2, Power Board Bsf-400

    (see manual) BPS-410 L1.11 (Power Board F7 Battery BSF-400) BP-410/01 AH AH L1.3 L1.5 BP-405/01 Therm.+ AH AH 3 J25 Therm.- BATT Vcon asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 41...
  • Page 42: Connection Of Network Cables (Autronet)

    Ethernet 2 (panels and Ethernet switches) throughout the entire system. Ethernet ports on Controller Board BSA-400 Ethernet 2 Ethernet 1 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 42...
  • Page 43: Autronet Single Star Topology

    Connecting External Cables 10.6.2 AutroNet Single Star Topology As an option, AutroSafe 4 allows also single Ethernet connections to one or several panels in a system if redundancy is not required. Ethernet 1 must always be used for single Ethernet connections.
  • Page 44: Autronet Ring Topology

    A ring topology is a redundant network, as all panels will continue to operate even with a single break or short-circuit on the ring. Ethernet ports on Controller Board BSA-400 Ethernet 2 Ethernet 1 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 44...
  • Page 45: Connection To Controller Board Bsa-400

    Shielded or armoured cable must be used for the 24V DC power supply. Note: For information on common earth connections for Power Cabinet STX Range, refer to documentation listed in chapter 6.6. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 45...
  • Page 46: Rs-485 Connections To Terminal Block, List L1

    10.9 RS-232 Connections to Terminal Block, List L1 Terminal block list L1 RS-232 L1.12 RS-232 TX RS-232 RX L1.14 RS-232 RX RS-232 TX L1.16 Serial Reference Serial Reference asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 46...
  • Page 47: Power Connections

    +24V In 1 A1 + J18.2 0V In 1 A1 0V Interconnection J18.3 +24V In 2 A1 + J18.4 0V In 2 A1 0V asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 47...
  • Page 48: Connections To Power Board Bsf-400

    External equipment. 3 seconds break at initialization of panel. +24V DC / 2A External equipment. 3 seconds break at initialization of panel. Output Connections to asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 48...
  • Page 49: Power Connection Overview

    * External panels type BU-BV-420 and BS-430 can be connected both to output A and B. Devide total power to both A and B. ------ Connected if needed. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 49...
  • Page 50: Mains Power Connections

    Note that the isolation must be kept on the mains cable as close up to the terminal points (L, N and ) as possible. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS...
  • Page 51: Installing I/O Modules

    11.2 Front View of I/O Module Front view when mounted on rail Screw terminal 10 Screw terminal 1 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 51...
  • Page 52: Mounting / Removing I/O Modules

    When the system is to be configured at a later point, note that the AutroSafe Configuration Tool graphically shows the first module on the top of the figure and the following in descending order. This may be opposite to the physical mounting, and must be taken into consideration when configuring the system.
  • Page 53: Removing

    Before connecting cables, make sure that the mains power is not connected. 11.4 Data Sheets - I/O Modules The AutroSafe User Documentation provides data sheets for I/O modules, including a short description of the I/O module, its application, plus technical specifications and cabling.
  • Page 54: Dual Safety Installation

    12. Dual Safety Installation 12.1 Dual Safety System Overview An AutroSafe system using the Dual Safety concept consists of a Primary System and a Secondary System. The purpose of the concept is to ensure that the Secondary System takes over the control of the detection loops if the Primary System or parts of it is lost for any reason.
  • Page 55: Example 1: Connections Using Al_Com+ Only

    Module is less than 3 meters. An AL_Com+ flat ribbon cable is used between the panel AL_Com port and the I/O stack (including the Secondary Loop Driver Module). asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 55...
  • Page 56: Example 2: Connections Using Both Al_Com+ And Autrofieldbus

    310) and the detection loop (one belonging to the Primary System and one belonging to the Secondary System) and thus controlling/providing the loop controller access to the detection loop. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 56...
  • Page 57 Dual Safety Installation asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 57...
  • Page 58: Connections - Autrokeeper Bn-180

    Primary: Active, Secondary: Standby – automatic actions disabled) When switched to On or Off the unit will be reset within 5 seconds asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 58...
  • Page 59: Cable Specifications

    Cable Specifications 13. Cable Specifications For the complete information on cable specifications, refer to Cable Specifications, part number 116-P-ASIFGCABLESPEC/CGB (file name: asafeifgcable_cgb). asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 59...
  • Page 60: Service And Maintenance

    Service and Maintenance 14. Service and Maintenance 14.1 Introduction The AutroSafe Interactive Fire Alarm System provides a Log Menu, which records all system events, i.e. fire alarms, prealarms, faults, enablements/disablements, user operations and tests. It is the system owner’s or authorized personnel’s duty to register all events in a Control Journal.
  • Page 61: Annual Service And Maintenance

    Check the alarm transference outputs by connecting from outgoing outputs (potential free relay and 24V output) activated by alarm in a zone. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 61...
  • Page 62: Fuse Replacements

    4 years (refer to manufacture date indicated on the battery). If a fault arises on the panel that cannot be rectified, contact your nearest Autronica Fire and Security office for qualified assistance. 14.6 Testing To ensure that the system works properly during normal operation after...
  • Page 63: Safety Measures During Commissioning And Maintenance

    14.8 SIL2 Approved Systems For SIL2 approved systems, service and maintenance shall be carried out according to the proof test intervals stated on the AutroSafe 4 Oil&Gas SIL2 (G2) certificate with registration number 44 207 11 555929-001.
  • Page 64: Appendix A - Controller Board Bsa_400A

    Appendix A - Controller Board BSA_400A 15. Appendix A - Controller Board BSA_400A 15.1 Circuit Board Layout asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 64...
  • Page 65: Location Inside Fire Alarm Control Panel Bs-420

    • Interface for the connection of display and front board • Panel Operational State output asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 65...
  • Page 66: Internal Led Indicators

    A1 + J18.2 0V In 1 A1 0V Interconnection J18.3 +24V DC In 2 A2 + J18.4 0V In 2 A2 0V asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 66...
  • Page 67: Two-Stage Push Button Reset (S5)

    The ports are to be used for connection of an optional printer or a memory stick. Each USB host port is limited to a maximum of 100mA load. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 67...
  • Page 68: Multifunction Serial Port Connector J3 - Autrofieldbus And Fault Relay

    Fault Relay Common L1.20 The built-in AutroFieldBus Master driver serves as a communication protocol between the AutroSafe panel, the BSD-340 PowerLoop drivers and BSD-321 protocol converters, plus Power Board BSF-400. It provides a redundant field bus system with a ring loop topology.
  • Page 69: Autrofieldbus Connections

    The AutroFieldBus cable is normally 2-wire twisted pair category 5 copper cables, however, fibre optic cable is possible by use of separate signal converters. The AutroFieldBus uses the same guidelines as AUTROLON (AutroSafe version 3.8 and earlier), in terms of cable lengths, fibre modem and boosters. 15.9 AutroFieldBus Connections 15.9.1 14.9.1 Ribbon Cable Connector BSA-400 to Terminal Block L1...
  • Page 70: Multifunction Serial Port Dipswitch Settings - Switch S6

    1 2 3 Switch RS-232 RS-422 RS-485 S6.1 Not applicable S6.2 Not applicable S6.3 Not applicable 15.11 CAN Bus Termination Dipswitch Settings - Switch asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 70...
  • Page 71: Rs-485 Connections

    15.12.1 Ribbon Cable Connector BSA-400 to Terminal Block L1 15.12.2 Switch Setting – Switch S6 and S1 Switch RS-485 Switch RS-485 S6.1 S6.2 S6.3 S1.4 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 71...
  • Page 72: Rs-422 Connections

    15.13.2 Switch Setting – Switch S6 and S1 Switch RS-422 S6.1 S6.2 S6.3 S1.1 S1.4 Switch RS-422 15.13.3 Schematic of port equivalent: +5v_SER_0 TX_422_X+ TX_422_Z- RX_422_A+ RX_422_B- Signal Reference asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 72...
  • Page 73: Rs-232 Connections

    Not applicable S6.3 Not applicable S1.4 Not applicable Switch RS-232 15.15 Serial Debug Connector J21 A standard AutroSafe programming cable XJA-029 is to be connected to this connector. The interface uses RS-232 115,2kbaud 8N1. BSA-400 Connector Description Communication Parameters J21.1...
  • Page 74: Al_Com+ Connector J5

    BSA-400 Connector Description J17.1 Backlight LED + 5V DC J17.2 Backlight LED - J17.3 Backlight LED - Backlight LED – 0V J17.4 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 74...
  • Page 75: Ethernet Ports (Rj-45 Connectors)

    15.18.1 Ethernet Straight Through Cable Name Cable Color Name White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown ame Pin Cable Color Pin Name asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 75...
  • Page 76: Appendix B - Power

    F2AL S2, Start on standby source (see manual) F7 Battery BP-410/01 AH AH BP-405/01 Therm.+ AH AH 3 J25 Therm.- BATT Vcon asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 76...
  • Page 77: Description

    The fault relay is energized as standard with its own watchdog. The power board provides power to AutroSafe, AutroSafe’s existing I/O module stacks, battery monitoring and charging, plus 24 voltage contacts for other external equipment.
  • Page 78: Batteries

    Charge current is also controlled, so that the charging voltage will decrease when the charge current reaches 2A. A “Battery voltage too low”-warning will display on AutroSafe systems connected to the BPS-410 via AutroFieldBus. The message will clear when charge current drops below 400mA.
  • Page 79: Button S2 - Start On S2 On Standby Source

    S2, Start on standby source (see manual) F7 Battery BP-410/01 AH AH BP-405/01 Therm.+ AH AH 3 J25 Therm.- BATT Vcon Start on standby source asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 79...
  • Page 80: Configuration Settings

    Dipswitch S6 S2, Start on standby source (see manual) F7 Battery BP-410/01 AH AH BP-405/01 Therm.+ AH AH 3 J25 Therm.- BATT Vcon asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 80...
  • Page 81: Dipswitch Table - S5 And S6

    S6.4 Not used S6.5 Battery ON: Battery connected Batteries must always be connected. S6.6 Power Unit Type ON: BPS-405 (obsolete) OFF: BPS-410 asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 81...
  • Page 82: Connector Description Bps-410

    Output C These will be turned OFF during start-up of BSF-400 (initialization). May be switched OFF/ON from AutroSafe. Power to I/O modules. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 82...
  • Page 83: Fault Relay Watchdog J26

    (E-68) Description All blinking LEDs, except where otherwise stated, will blink with 0,5 seconds ON and 0,5 seconds OFF. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 83...
  • Page 84: Battery Resistance Measurement

    3 times with ~50s interval between each try. If an external fault is not resolved, BSF-400 will not try to re-power more than 3 times. A reset on an AutroSafe panel or pushing reset button S1 will force the BSF-400 to retry.
  • Page 85: Part Of An Autrofieldbus Network

    AutroFieldBus. Diagnostic outputs are given onboard with LEDs and alarm relay, and on AutroSafe panels with audible alarms and display messages. The LEDs and fault relay will not indicate any failure before the AutroSafe has AutroFieldBus connection and the AutroSafe system has been initialized.
  • Page 86: Appendix B - Fault Messages Power Board Bsf_400

    BSF-400 Battery Relay Fault This warning may occur Connect battery, or put during start-up if a dip switch 5 to OFF asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 86...
  • Page 87 400mA. i.e. charging current is >1100mA. Fault category: Por Fau message Cause Remedy asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 87...
  • Page 88: Appendix C - Bp_405 (Obsolete)

    18. Appendix C – BP_405 (Obsolete) 18.1 Mounting Power Cabinet BP-405 (obsolete) AutroSafe Release 4 provides a Power Cabinet BP-405 with space for two 12V/18Ah batteries (not included). The power supply and battery brackets are already mounted when the cabinet is delivered from the factory.
  • Page 89 Connect the red cable ◼ from the connector on the Power Board to the plus pole on the lowermost battery. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 89...
  • Page 90 230VAC or 24VDC. asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS Page 90...
  • Page 91: Power Cabinet And Power Units

    Appendix C – BP_405 (Obsolete) 18.2 Power Cabinet and Power Units AutroSafe 4 provides the following power cabinet and power units: • Power Cabinet BP-405 (obsolete) • Power Unit BPS-405 (obsolete) 18.2.1 Power Cabinet BP-405 (OBSOLETE) The Power Cabinet BP-405 contains the following: •...