Installation Handbook High sensitivity aspirating smoke detector AutroSense Micra 100 . E, 2017-05-02 116-P-ASMICRA100/DE, Rev , Autronica Fire And Security AS...
Page 2
Product names mentioned in this publication may be trademarks. They are used only for identification. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 2...
Introduction 1. Introduction 1.1 General AutroSense Micra 100 is a highly sophisticated ‘next generation‘ of high Sensitivity Aspirating Smoke Detection product that has been designed to ensure that installation and commissioning is as simple as possible, while optimising performance. AutroSense Micra 100 incorporates a patented ‘artificial intelligence‘...
Class A, B and C Technical data: see INF48027 held by the manufacturer Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 2...
The OK lamp will flash during the 15 minute Fastlearn period when the detector is first learning about its environment. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 3...
3. Addressable bus interface card (APIC) port 4. Detector address DIP switch 5. RS232 serial port 6. Fan relay board Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 4...
3. APIC addressable bus connections for use in conjunction with interface card 4. RS485 / SenseNET connections 5. Power supply connections 6. Connection to fan relay board Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 5...
Programming the detector 4. Programming the detector The AutroSense Micra 100 may be programmed from a PC when connected to the detector via a standard 9-pin serial lead connected to the serial port of the computer and the 9 way socket at the base of the detector ( ‘Connecting to a PC’).
This is backed up with a rechargeable battery. Later adjustments to the clock setting should not exceed ± 70 minutes unless a FastLearn is initiated. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 7...
5 seconds. 4.4 ClassiFire Override – “Alarm Levels and Delays” This function has no current use on the AutroSense Micra 100 but is reserved for future expansion purposes. 4.5 Alarm Factor – “Alarm Levels and Delays” Tab The detector sensitivity is set with this entry, which will also affect the probability of nuisance alarms.
To cancel demo mode, tick this box or power down and restart the detector to initiate FastLearn mode. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 9...
For this reason, the detector should not be left in Demo mode for normal use when connected to a fire-alarm panel. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
4.13 Remote Functions – “Alarm Actions” Tab, Remote Input Subgroup These functions have no current use on the AutroSense Micra 100 but are reserved for future expansion purposes. 4.14 Programmed Isolate (discontinued) This function is no longer supported.
The watchdog is a circuit built into the controller that restarts the controller in the event of a failure to function properly. This could be as Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02,...
See “Event log” for further details. 4.22 Device T ext – “Device Information” Tab This function has no current use on the AutroSense Micra 100 but is reserved for future expansion purposes. 4.23 Reference Detector – “Referencing” Tab An AutroSense Micra detector may use another detector as a fresh air reference.
4.30 Flow fault delay – Flow monitoring tab This feature requires the Remote Control Software version 3.2 or later. The default flow fault thresholds on the AutroSense Micra 100 are set to meet the stringent airflow monitoring requirements of EN 54-20, with a default flow fault delay of 30 seconds.
4.32 Chart Recording Rate – “Miscellaneous” Tab This function controls how frequently the detector and alarm level or flow rates are stored in the AutroSense Micra 100’s internal chart recorder log. (See “Chart recording”). The chart log recording rates are as follows.
It should be noted that where a ClassiFire alarm factor other than the default is required for the protected area, this will need to be reentered. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
To enter the histogram screen, either select the menu options “View Histogram viewer…” or click the symbol indicated below. bility of Nuisance Alarm Suggested Protected Area Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 17...
Page 23
Detector output: This shows the real-time variation in background smoke levels in terms of a percentage of full scale deflection. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
Chart recording files have the extension “.rcw”. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 19...
As a special case, if desiring to recall the factory default settings, there is a file named ‘default.dfs’ in the ‘remote2k’ directory. Loading this file will reset the detector to the factory default. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
This product employs a very low-power aspirator and the aspirating capability of the AutroSense Micra 100 detector is limited accordingly. AutroSense Micra 100 is NOT intended to protect large areas, or to sample from areas where there may be any difference in airflow rates or pressure differentials.
Page 27
Note: The piped exhaust docking station needs to be used in this case. Above ceiling sampling with detector mounted in ceiling void Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
Complex sampling pipe runs should be avoided with the AutroSense Micra 100 detector. The use of ‘T’ branch-pipes is not recommended. The AutroSense Micra 100 detector is fitted with two sampling pipe inlets as standard. It is always preferable to use two shorter pipes as opposed to one longer pipe.
If functions are changed, it is recommended that the system is retested if continuing compliance is in any doubt. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
Two port docking station Two port + pipe exhaust docking station Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 25...
The picture in Section 7.1 shows the location of the earth stud. Fix the earth wires in place with the nuts provided. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
The following illustration shows the power and signal connections to the docking station for connection to a single SenseNET cable. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 27...
Removing the detector is simply the reverse of this process, leaving the pipe-work and wiring connections installed in the docking station. Dock fixing screws Cover fixing screws Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 28...
Interfacing 8. Interfacing Because of the flexible nature of the AutroSense Micra 100 detector and the many possible configurations, there are many options for interfacing the detectors to the Fire-alarm panel. These include many third party interfaces available from various manufacturers.
Addresses chosen for detectors do not have to be consecutive or in a given order so long as they are all different. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
It will be noted that whereas the AutroSense 200 units have two input / output buses (1A / 1B and 2A / 2B), the AutroSense Micra 100 has only a single such bus (A / B) and therefore each bus terminal has an input and an output wire, compared with a single wire in each terminal in the AutroSense 200.
9 pin female `D` 9 pin female `D` connector connector Serial port connection to PC serial port Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 33...
Either select the menu options “View Event log” or click on the event log symbol as indicated below. The following screen appears: Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 34...
Page 40
“Alarms”. To tick all the boxes, tick “All”. Any or all of the event categories may be selected or deselected as desired. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 35...
24 hours whilst ClassiFire acclimatises to the protected environment and sets up appropriate day and night sensitivity settings. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
Maintenance 11. Maintenance AutroSense Micra 100 is a very low maintenance detection system. If required, external cleaning of the unit should be performed using a damp (not wet) cloth. Do not use solvents as these may mar the front panel label. The only part that may require field replacement during servicing is the dust separator assembly.
Page 43
Save As: Saves the summary list of scanned detectors and their status as a text (.txt) file. Print: Prints the summary list to a connected printer. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
If so, the chamber may require factory service. The detector is not designed to handle large quantities of coarse debris and dust. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
Technology Ltd PipeCAD® pipe modeling software prompts the use of appropriate end-caps. Open bore pipes are not recommended. Check that the high flow fault threshold is not set too low Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
Page 46
Test the response of the detector using aerosol synthetic smoke. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 41...
Page 47
This equipment is only to be used in accordance with this specification. Failure to operate the equipment as specified may cause damage to the unit. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
Page 49
AutroSense Micra_100 Specification . E, 2017-05-02 116-P-ASMICRA100/DE, Rev...
Page 51
United Technologies Corporation (UTC) and employs more than 380 people with great skill and experience in the developing, manufacturing and marketing of fire safety equipment. Autronica Fire and Security AS is an international company based in Trondheim, a dynamic city known as the technological hotspot of Norway.