Autronica AutroSense Micra 100 Installation Handbook

Autronica AutroSense Micra 100 Installation Handbook

High sensitivity aspirating smoke detector
Table of Contents

Advertisement

Quick Links

Installation Handbook
High sensitivity aspirating smoke detector AutroSense Micra 100
. E, 2017-05-02
116-P-ASMICRA100/DE, Rev
, Autronica Fire And Security AS

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AutroSense Micra 100 and is the answer not in the manual?

Questions and answers

Summary of Contents for Autronica AutroSense Micra 100

  • Page 1 Installation Handbook High sensitivity aspirating smoke detector AutroSense Micra 100 . E, 2017-05-02 116-P-ASMICRA100/DE, Rev , Autronica Fire And Security AS...
  • Page 2 Product names mentioned in this publication may be trademarks. They are used only for identification. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 2...
  • Page 3: Table Of Contents

    4.29 Flow Low Limit – “Flow Monitoring” Tab ..........14 4.30 Flow fault delay – Flow monitoring tab ..........14 4.31 Access Code – “Miscellaneous” Tab ..........14 Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 4 12.4 Detector Sensitivity Varies Over Time ..........40 12.5 Flow Fault Errors ................40 12.5.1 "Low flow" Error Messages............. 40 Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 2...
  • Page 5 12.5.2 "High flow" Error Messages............. 40 13. Do’s and Don’ts ............... 41 13.1 DO ..................... 41 13.2 DON’T....................41 14. AutroSense Micra_100 Specification ......42 Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 6: Introduction

    Introduction 1. Introduction 1.1 General AutroSense Micra 100 is a highly sophisticated ‘next generation‘ of high Sensitivity Aspirating Smoke Detection product that has been designed to ensure that installation and commissioning is as simple as possible, while optimising performance. AutroSense Micra 100 incorporates a patented ‘artificial intelligence‘...
  • Page 7: Reference Documentation

    Class A, B and C Technical data: see INF48027 held by the manufacturer Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 2...
  • Page 8: Indicators

    The OK lamp will flash during the 15 minute Fastlearn period when the detector is first learning about its environment. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 3...
  • Page 9: Inside The Detector

    3. Addressable bus interface card (APIC) port 4. Detector address DIP switch 5. RS232 serial port 6. Fan relay board Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 4...
  • Page 10: Detector Terminal Block Connections

    3. APIC addressable bus connections for use in conjunction with interface card 4. RS485 / SenseNET connections 5. Power supply connections 6. Connection to fan relay board Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 5...
  • Page 11: Programming The Detector

    Programming the detector 4. Programming the detector The AutroSense Micra 100 may be programmed from a PC when connected to the detector via a standard 9-pin serial lead connected to the serial port of the computer and the 9 way socket at the base of the detector ( ‘Connecting to a PC’).
  • Page 12: Time And Date - "Time And Date" Tab

    This is backed up with a rechargeable battery. Later adjustments to the clock setting should not exceed ± 70 minutes unless a FastLearn is initiated. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 7...
  • Page 13: Alarm Levels - "Alarm Levels And Delays" Tab, Level Subgroup

    5 seconds. 4.4 ClassiFire Override – “Alarm Levels and Delays” This function has no current use on the AutroSense Micra 100 but is reserved for future expansion purposes. 4.5 Alarm Factor – “Alarm Levels and Delays” Tab The detector sensitivity is set with this entry, which will also affect the probability of nuisance alarms.
  • Page 14: Ldd Enable - "Alarm Levels And Delays" Tab

    To cancel demo mode, tick this box or power down and restart the detector to initiate FastLearn mode. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 9...
  • Page 15: Auto Fastlearn Enable - "Alarm Levels And Delays" Tab

    For this reason, the detector should not be left in Demo mode for normal use when connected to a fire-alarm panel. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 16: Day Start / Night Start - "Day/Night Switching" Tab

    4.13 Remote Functions – “Alarm Actions” Tab, Remote Input Subgroup These functions have no current use on the AutroSense Micra 100 but are reserved for future expansion purposes. 4.14 Programmed Isolate (discontinued) This function is no longer supported.
  • Page 17: Latching Alarms - "Alarm Actions" Tab

    The watchdog is a circuit built into the controller that restarts the controller in the event of a failure to function properly. This could be as Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02,...
  • Page 18: Device T Ext - "Device Information" Tab

    See “Event log” for further details. 4.22 Device T ext – “Device Information” Tab This function has no current use on the AutroSense Micra 100 but is reserved for future expansion purposes. 4.23 Reference Detector – “Referencing” Tab An AutroSense Micra detector may use another detector as a fresh air reference.
  • Page 19: Flow High Limit - "Flow Monitoring" Tab

    4.30 Flow fault delay – Flow monitoring tab This feature requires the Remote Control Software version 3.2 or later. The default flow fault thresholds on the AutroSense Micra 100 are set to meet the stringent airflow monitoring requirements of EN 54-20, with a default flow fault delay of 30 seconds.
  • Page 20: Chart Recording Rate - "Miscellaneous" Tab

    4.32 Chart Recording Rate – “Miscellaneous” Tab This function controls how frequently the detector and alarm level or flow rates are stored in the AutroSense Micra 100’s internal chart recorder log. (See “Chart recording”). The chart log recording rates are as follows.
  • Page 21: Separator Change Date - "Miscellaneous" Tab

    It should be noted that where a ClassiFire alarm factor other than the default is required for the protected area, this will need to be reentered. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 22: Other Remote Software Features

    To enter the histogram screen, either select the menu options “View Histogram viewer…” or click the symbol indicated below.  bility of Nuisance Alarm Suggested Protected Area Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 17...
  • Page 23 Detector output: This shows the real-time variation in background smoke levels in terms of a percentage of full scale deflection. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 24: Chart Recording

    Chart recording files have the extension “.rcw”. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 19...
  • Page 25: Load/Save Function Settings

    As a special case, if desiring to recall the factory default settings, there is a file named ‘default.dfs’ in the ‘remote2k’ directory. Loading this file will reset the detector to the factory default. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 26: Design Limitations

    This product employs a very low-power aspirator and the aspirating capability of the AutroSense Micra 100 detector is limited accordingly. AutroSense Micra 100 is NOT intended to protect large areas, or to sample from areas where there may be any difference in airflow rates or pressure differentials.
  • Page 27 Note: The piped exhaust docking station needs to be used in this case. Above ceiling sampling with detector mounted in ceiling void Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 28: System Design

    Complex sampling pipe runs should be avoided with the AutroSense Micra 100 detector. The use of ‘T’ branch-pipes is not recommended. The AutroSense Micra 100 detector is fitted with two sampling pipe inlets as standard. It is always preferable to use two shorter pipes as opposed to one longer pipe.
  • Page 29: 54-20 Compliance

    If functions are changed, it is recommended that the system is retested if continuing compliance is in any doubt. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 30: Installation

    Two port docking station Two port + pipe exhaust docking station Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 25...
  • Page 31: Mechanical Installation

    The picture in Section 7.1 shows the location of the earth stud. Fix the earth wires in place with the nuts provided. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 32: Signal Connections

    The following illustration shows the power and signal connections to the docking station for connection to a single SenseNET cable. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 27...
  • Page 33: Final Installation

    Removing the detector is simply the reverse of this process, leaving the pipe-work and wiring connections installed in the docking station. Dock fixing screws Cover fixing screws Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 28...
  • Page 34: Interfacing

    Interfacing 8. Interfacing Because of the flexible nature of the AutroSense Micra 100 detector and the many possible configurations, there are many options for interfacing the detectors to the Fire-alarm panel. These include many third party interfaces available from various manufacturers.
  • Page 35: Address Table

    Addresses chosen for detectors do not have to be consecutive or in a given order so long as they are all different. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 36: Connecting A Autrosense Micra 100 To A Sensenet/Rs485 Detector Network

    It will be noted that whereas the AutroSense 200 units have two input / output buses (1A / 1B and 2A / 2B), the AutroSense Micra 100 has only a single such bus (A / B) and therefore each bus terminal has an input and an output wire, compared with a single wire in each terminal in the AutroSense 200.
  • Page 37: Connection To Autrosafe

    8.4 Connection to BS-systems AS Micra BN-35 1 2 3 4 5 6 1 2 3 4 5 6 Detector loop Detector loop Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 32...
  • Page 38: Connecting To A Pc

    9 pin female `D` 9 pin female `D` connector connector Serial port connection to PC serial port Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 33...
  • Page 39: Event Log

    Either select the menu options “View Event log” or click on the event log symbol as indicated  below. The following screen appears: Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 34...
  • Page 40 “Alarms”. To tick all the boxes, tick “All”. Any or all of the event categories may be selected or deselected as desired. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 35...
  • Page 41: Commissioning

    24 hours whilst ClassiFire acclimatises to the protected environment and sets up appropriate day and night sensitivity settings. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 42: Maintenance

    Maintenance 11. Maintenance AutroSense Micra 100 is a very low maintenance detection system. If required, external cleaning of the unit should be performed using a damp (not wet) cloth. Do not use solvents as these may mar the front panel label. The only part that may require field replacement during servicing is the dust separator assembly.
  • Page 43 Save As: Saves the summary list of scanned detectors and their status as a text (.txt) file. Print: Prints the summary list to a connected printer. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 44: Troubleshooting

    If so, the chamber may require factory service. The detector is not designed to handle large quantities of coarse debris and dust. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 45: Detector Sensitivity Varies Over Time

    Technology Ltd PipeCAD® pipe modeling software prompts the use of appropriate end-caps. Open bore pipes are not recommended. Check that the high flow fault threshold is not set too low Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 46  Test the response of the detector using aerosol synthetic smoke. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security Page 41...
  • Page 47 This equipment is only to be used in accordance with this specification. Failure to operate the equipment as specified may cause damage to the unit. Installation Handbook, High sensitivity aspirating smoke detector AutroSense Micra 100, 116-P-ASMICRA100/DE, Rev. E, 2017-05-02, Autronica Fire and Security...
  • Page 49 AutroSense Micra_100 Specification . E, 2017-05-02 116-P-ASMICRA100/DE, Rev...
  • Page 51 United Technologies Corporation (UTC) and employs more than 380 people with great skill and experience in the developing, manufacturing and marketing of fire safety equipment. Autronica Fire and Security AS is an international company based in Trondheim, a dynamic city known as the technological hotspot of Norway.