Safety Limit Checklist
The following checklists are designed to assist the
service technician in analysis. However, because
there are many possible external problems, do not
limit your diagnosis to only the items listed.
Safety Limit #1
Freeze time exceeds 60 minutes for 3 consecutive
freeze cycles.
Possible Cause Checklist
Improper installation
Refer to "Installation/Visual Inspection Checklist"
on page 64
Water System
Water Level too high or defective float switch
(water escaping water trough)
Low water pressure (20 psig min.)
High water pressure (80 psig max.)
High water temperature (90°F/32.2°C max.)
Clogged water distribution tube
Dirty/defective water inlet valve
Defective water pump

Electrical System

Harvest cycle not initiated electrically
Contactor not energizing
Compressor electrically non-operational
Restricted condenser air flow
High inlet air temperature (110°F/43.3°C max.)
Condenser discharge air re-circulation
Dirty condenser fins
Defective fan cycling control
Defective fan motor
Low water pressure (20 psig min.)
High water temperature (90°F/32.2°C max.)
Dirty condenser
Part Number STH042 3/14