Water System Checklist

A water-related problem often causes the same
symptoms as a refrigeration system component
malfunction.
Example: A water dump valve leaking during the
freeze cycle, a system low on charge, and a starving
TXV have similar symptoms.
Water system problems must be identified and
eliminated prior to replacing refrigeration components.
Water area (evaporator) is dirty
Clean as needed
Water inlet pressure not between 20 and 80 psig
(1–5 bar, 138–552 kPa)
Install a water regulator valve or increase the
water pressure
Incoming water temperature is not between 35°F
(1.7°C) and 90°F (32.2°C)
If too hot, check the hot water line check valves in
other store equipment
Water filtration is plugged (if used)
Install a new water filter
Vent tube is not installed on water outlet drain
See Installation Instructions
Hoses, fittings, etc., are leaking water
Repair/replace as needed
Water valve is stuck open, closed or is leaking
Clean/replace as needed
Water is spraying out of the sump trough area
Stop the water spray
Uneven water flow across the evaporator
Clean the ice machine
Water is freezing behind the evaporator
Correct the water flow
Plastic extrusions and gaskets are not secured to
the evaporator
Remount/replace as needed
Part Number STH042 3/14