6.2.2 Range of usage & limitations
Item
Indoor intake air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Indoor units
Number of connected units
that can be
used in
Total of indoor units (class kW)
combination
Total length for all rooms
Length for one indoor unit
Difference in
When above outdoor unit (B)
height between
indoor and outdoor
When below outdoor unit (A)
units
Difference in height between indoor units (C)
Compressor
1 cycle time
stop/start
frequency
Stop time
Voltage fluctuation
Power source
Voltage drop during start
voltage
Interval unbalance
A
B
198
Model
6 min or more (from stop to stop or from start to start)
C
SCM45ZA
Refer to the selection chart.
1 to 2 units
6.5kW
Max. 30m
Max. 25m
Max. 10m
Max. 15m
Max. 25m
3 min or more
Within ±10% of rated voltage
Within ±15% of rated voltage
Within ± 3% of rated voltage