To exit Configuration Mode use the * key to cycle through all options – Configuration
Mode will exit after the final option. Configuration Mode will exit automatically if no key is
pressed for 15 seconds.
Configuration options and their default values can be seen in Table 1: Configuration
options and default values.
Table 1: Configuration options and default values
Option
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
* Use the Mute key to reset alarm and ventilation values.
10
Description
Ventilation level 1
Ventilation level 2
Ventilation level 3
Relay alarm activated with alarm
Relay alarm activated with fault
Relay alarm activated with ventilation
Relay alarm deactivated with mute
Missing detector detection
Number of alarms detected *
Number of ventilations performed *
Delay time for Mode key (in seconds)
Confirmation delay to activate ventilation
(in seconds)
Confirmation delay to deactivate ventilation
(in seconds)
Idle time to exit * mode (in seconds)
Confirmation time to alarm activation
(in seconds)
Confirmation time to fault activation
(in seconds)
Number of detectors in loop
Default value
50
100
150
ON
OFF
OFF
ON
OFF
0
0
20
60
120
15
20
120
Calculated automatically
during test procedure after
system setup.
KM260 Series Carbon Monoxide Detection System