NTRODUCTION 1.1 General description The GE Interlogix carbon monoxide (CO) detection system is the ideal solution for detection of dangerous levels of CO gas in car parks and other enclosed spaces where levels of CO gas must be monitored and controlled effectively.
Three zone line terminals: positive, negative and data. See Figure 2: Line connection. Three terminals for the ventilation output relay (EXTR. 1): common (C), normally open (NO), normally closed (NC).. Three terminals for the alarm output relay: common (C), normally open (NO), normally closed (NC). KM260 Series Carbon Monoxide Detection System...
Press the Test key. This will verify the proper working of the LED display, the zone module LED indicators and the acoustic buzzer. The number of detectors installed in the zone will also be assessed. Any fault discovered will be indicated. KM260 Series Carbon Monoxide Detection System...
Power on-off key / LED 100 PPM LED Mute key / LED 50 PPM LED Test key Level key * (star) key Automatic mode LED Alarm LED Manual mode LED Ventilation LED Stopped LED Fault LED Mode key KM260 Series Carbon Monoxide Detection System...
Exit alarm or fault indication by pressing the * key. Indication will exit automatically if no key is pressed for 15 seconds. Level key Used to set the CO concentration level that will trigger the ventilation relay output. KM260 Series Carbon Monoxide Detection System...
1 (Ventilation level 1) is displayed. Use the Level, Mode and Mute keys to modify numeric values. Use the Mute key to modify on / off values. The * key confirms the entry and displays the next option. KM260 Series Carbon Monoxide Detection System...
Page 10
Confirmation time to alarm activation (in seconds) Confirmation time to fault activation (in seconds) Number of detectors in loop Calculated automatically during test procedure after system setup. * Use the Mute key to reset alarm and ventilation values. KM260 Series Carbon Monoxide Detection System...
The log book should be referred to regularly to ensure all faults have been repaired. The useful lifespan of GE Interlogix CO detectors is 4 years. Detectors and / or sensing elements must be serviced or replaced within this time frame.
Ventilation modes ..............automatic, manual, stopped Ventilation mode indication................LED indicator Alarm indication ................acoustic and LED indicator Fault warning indication ..............acoustic and LED indicator Operating temperature....................0 to 60ºC Storage temperature ................... -10 to 70ºC Maximum humidity ......................95% KM260 Series Carbon Monoxide Detection System...