5 T
S
ECHNICAL
PECIFICATIONS
Cabinet size (1 or 2 zones).....................................................275 mm x 335 mm x 130 mm
Cabinet size (3 to 5 zones) .....................................................470 mm x 335 mm x 130 mm
Mains power supply ........................................................................... 230 VAC ±10% / 95W
Maximum consumption................................................................. 100 mA per zone module
Mains fuse................................................................................................. 500 mA 5x20 mm
Zone module input voltage .................................................................................... 9-23 VAC
Number of relays............................................................................................. 3 (C, NO, NC)
Maximum line length ....................................................................................................350 m
Maximum number of detectors per zone ...........................................................................15
Measurement range.........................................................................................0 to 300 PPM
Programmable alarm level...............................................................................0 to 295 PPM
Selectable ventilation relay levels.............................................................50, 100, 150 PPM
LED Display ............................................................................................................... 3 digits
Ventilation level indication ............................................................................... LED indicator
Ventilation modes ..................................................................... automatic, manual, stopped
Ventilation mode indication.............................................................................. LED indicator
Alarm indication ..........................................................................acoustic and LED indicator
Fault warning indication ..............................................................acoustic and LED indicator
Operating temperature............................................................................................0 to 60ºC
Storage temperature ........................................................................................... -10 to 70ºC
Maximum humidity ......................................................................................................... 95%
12
KM260 Series Carbon Monoxide Detection System