Mitsubishi SCM40ZJ-S Service Manual page 188

Outdoor & indoor unit inverter multi-split system, residential air conditioners (split system, air to air heat pump type)
Hide thumbs Also See for SCM40ZJ-S:
Table of Contents

Advertisement

CAUTION
During the installation, do not lean on the control box or the display, as they may be damaged.
Fixing of indoor unit
Install the indoor unit on flat wall. If improperly installed, it may cause abnormal noise and vibration. (Distortion on the wall shall be no larger than 3 mm.)
Floor installation
Secure using upper 2 screws for floor installations.
If possible, also attach two lower screws.
If there is an obstacle such as a cable cover,
cut off the hatched part before installation.
CONNECTION OF REFRIGERANT PIPINGS
Preparation
Keep the openings of the pipes covered with tapes etc. to prevent dust, sand, etc.
from entering them.
Indoor
(Do not turn)
A
Remove
Press
Remove the flared nuts. (on both liquid and gas sides)
Install the removed flared nuts to the pipes to
be connected,then flared the pipes.
CAUTION
Do not apply refrigerating machine oil to the flared surface.
 Flaring work
Clutch type flare tool for
Measurement B
Copper pipe diameter
R410A
ø6.35
0.0 - 0.5
ø9.52
0.0 - 0.5
ø12.7
0.0 - 0.5
Flaring
Use a flare tool designed for R410A or a conventional flare tool.
block
Please note that measurement B (protrusion from the flaring block) will vary depending
Copper pipe
on the type of a flare tool in use.
If a coventional flare tool is used, please use a copper pipe gauge or a similar
instrument to check protrusion so that you can keep measurement B to a correct value.
ELECTRICAL WIRING WORK
Preparation of indoor unit
Mounting of connecting wires
1
Remove the fixing screw of clamp.
2
Connect the connecting wire securely to the terminal block.
1 ) Connect the connection wire securely to the terminal
block. If the wire is not affixed completely, contact will be
poor, and it is dangerous as the terminal block may heat
up and catch fire.
2 ) Take care not to confuse the terminal numbers for indoor
and outdoor connections.
3
Fix the connecting wire by wiring clamp.
4 Pass the connecting wire through the wiring holder.
Wall installation
At first secure the installation board using 5 screws and the indoor unit using 2 screws.
Installation of Installation board
Look for the inside wall structures (Intersediats
support or pillar and finally install the unit after level
surface has been checked.)
Fixing on concrete wall
Use of nut anchor
Bolt
(M6 12)
Installation
board
CAUTION
Be careful not to stress the connecting refrigerant pipes.
(Do not pull with a force of larger than 5 kgf.)
Connection
Indoor
Liquid side
Dimension A
Gas side
Liquid side ø6.35:9.1(mm)
Gas side ø9.52:13.2(mm)
ø12.7:16.6(mm)
CAUTION
Do not apply excess torque to the flared nuts. Otherwise, the flared nuts may check depending.
Insulation of the connection portion
Pass the refrigerant pipe through the piping hole to
Measurement B (mm)
indoor side.
Conventional (R22) flare tool
Arrange the pipes according to the direction of piping.
Clutch type
Wing nut type
1.0 - 1.5
1.5 - 2.0
1.0 - 1.5
1.5 - 2.0
155
105
1.0 - 1.5
2.0 - 2.5
45
130
Position it so that the slit area faces upward.
140
CAUTION
During installation, do not lean on the control box or the display, as they
may be damaged.
CAUTION
Pass the connecting wire securely through the wiring holder. If it passes
In case of faulty wiring connection, the indoor unit
on the sensor, it may not detect suction temperature and/or humidity.
stops, and then the run lamp turns on and the timer
lamp blinks.
Use cables for interconnection wiring to avoid
loosening of the wires.
CENELEC code for cables Required field cables.
H05RNR4G1.5 (example) or 245IEC57
H
Harmonized cable type
05
300/500 volts
R
Natural-and/or synth, rubber wire insulation
N
Polychloroprene rubber conductors insulation
R
Stranded core
4or5
Number of conductors
G
One conductor of the cable is the earth
conductor (yellow/green)
1.5
Section of copper wire (mm
)
2
Tapping screw
Standard hole
Adjustment of the installation board in the horizontal
direction is to be conducted with five screws in a temporary
tightened state.
Adjust so the board will be level by turning the board with
the standard hole as the center.
Finishing work and fixing
Connect the pipes on both liquid and gas sides.
(Do not turn)
Tighten the nuts to the following torque.
Liquid side (ø6.35) : 14.0 - 18.0 N·m (1.4 - 1.8 kgf·m)
Gas side (ø9.52)
: 34.0 - 42.0 N·m (3.4 - 4.2 kgf·m)
(ø12.7)
: 49.0 - 61.0 N·m (4.9 - 6.1 kgf·m)
Cover the coupling with insulator and then cover it with tapes.
Use an attached
pipe cover for heat insulation.
Refrigerant
Refrigerant
pipe
pipe
Slit
Slit
Add
Tape
⑩band
How to fit the front panel
 Fitting
1
Do remove the air filter.
2
Cover the body with the front panel.
Fit the 6 latches in the lower section.
3
then 3 latches in the upper section.
4
Tighten the 5 set screws.
5
Fit the air filter.
6
Fit the air inlet panel.
Terminal block
Close and attachment of the air inler panel
 To close, attach the panel after pulling
the strings, hold the panel at both ends of
upper part to lower downward and push it
Clamp
slightly until the latch works.
Fixing screw
Wiring holder
Sensor
When practicing the half-console, make sure to fix the unit securely.
Otherwise, it could fall.
Refrigerant piping
Connection wiring,
Cover the exterior portion with outer tape
Earth wiring
and shape the piping so it will match the
Outer tape
contours of the route that the piping to take.
Also fix the wiring and pipings to the wall
Drain hose
with clamps.
Wood screw
Clamp
CAUTION
If heat insulation is insufficient, water leakage
may occur. In addition, the room temperature
sensor may give a false alert due to heat
Refrigerant
radiation from the pipes.
pipe
 Cover the indoor unit's flare-connected joints, after
they are checked for a gas leak, with an indoor unit
⑨Pipe cover
heat insulating material and then wrap them with a
tape with an attached
pipe cover placed over the
heat insulating material's slit area.
Latch
Latch

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents