Mitsubishi SCM40ZJ-S Service Manual page 113

Outdoor & indoor unit inverter multi-split system, residential air conditioners (split system, air to air heat pump type)
Hide thumbs Also See for SCM40ZJ-S:
Table of Contents

Advertisement

Error code
E16
Remote controller:
1. Applicable model
FDTC and FDUM series only
2. Error detection method
Detected by rotation speed of
indoor fan motor
3. Condition of Error displayed
When actual rotation speed of
indoor fan motor drops to lower
than 200rpm for 30 seconds
continuously, the compressor
and the indoor fan motor
stop. After 2-seconds, it starts
again automatically, but if this
error occurs 4 times within
60 minutes after the initial
detection.
4. Presumable cause
• Defective indoor power PCB
• Foreign material at rotational
area of fan propeller
• Defective fan motor
• Dust on control PCB
• Blown fuse
• External noise, surge
Note:
LED
Green
Red
Keeps flashing 1 time flash
Indoor
Stays OFF
Outdoor
5. Troubleshooting
Diagnosis
Does any
foreign material
intervene in rotational area
of fan propeller?
NO
Does the fan
rotate smoothly when turned
by hand?
YES
Is DC280V
detected between �-� of
fan motor connector
CNM?
YES
Power supply reset
Is it normalized?
112
-
Content
Indoor fan motor anomaly
( FDTC and FDUM series )
YES
NO
Note (1) � for GND
1
NO
Is the fuse F202
NO
FDUM: F3 blown?
YES
NO
YES
-
'11 • SCM-SM-110
Countermeasure
Remove foreign material.
Replace the fan motor.
Check power voltage.
Replace faulty fan motor
and power PCB.
Replace fan motor. (If the
error persists after replacing
the fan motor, replace the
indoor control PCB.)
Malfunction by temporary
noise

Hide quick links:

Advertisement

Table of Contents
loading