FLUE SYSTEMS
INSTALLING THE HORIZONTAL
FLUE TERMINAL
NOTE: The horizontal flue terminal supplied may be used
through outside walls up to 600mm (24in) thick.
1. Horizontal flue Terminal (Through the Wall) supplied
a) Cut an opening of at least 165mm (6.5in) diameter
through to the outside.
Hole through wall
Flue terminal
Outer wall
mount plate
4 Fixing screws
(supplied)
Air intake openings
(must face ground)
Fig. 4
4 Wall anchors
c) Slide the outside wall plate over the flue terminal and
fasten to the wall with four screws. Depending on the
wall construction, wall anchors may be required to
reinforce the screws.
Hole through wall
Flue terminal
Inner wall mount
plate
4 Fixing screws
(supplied)
Fig. 2
4 Wall anchors
INSTALLATION • SECTION 3
b) Slide the flue terminal through the wall opening to the
rib closest to the intake air openings of the terminal
and even with the outside wall.
d) Install inside wall plate on the inside wall and secure
with four screws. Depending on wall construction,
wall anchors may be required to reinforce the screws.
25