Dimensions And Service Space; Dimensions Of Outdoor Unit - Daikin RYYQ8T7Y1B Installation And Operation Manual

Vrv iv system air conditioner
Table of Contents

Advertisement

7.

Dimensions and service space

7.1.

Dimensions of outdoor unit

R(X/Y)(Y/M)Q8~12
76
76
97
137
765
(mm)
R(X/Y)(Y/M)Q14~20
76
97
76
137
765
(mm)
Installation and operation manual
9
766
4-15x22.5
107
272
328
373
930
1076
4-15x22.5
107
272
328
373
1240
7.2.
Service space
The space around the unit is adequate for servicing and the minimum
space for air inlet and air outlet is available (refer to the figure below
and choose one of the possibilities).
b
c
a
a
a
a
d
b
e
f
a
a
d
b
e
f
a
a
d
A+B+C+D
a≥10 mm
a≥50 mm
b≥300 mm
b≥100 mm
c≥10 mm
c≥50 mm
d≥500 mm
d≥500 mm
a≥10 mm
a≥50 mm
b≥300 mm
b≥100 mm
c≥10 mm
c≥50 mm
d≥500 mm
d≥500 mm
e≥20 mm
e≥100 mm
a≥10 mm
a≥50 mm
b≥300 mm
b≥100 mm
c≥10 mm
c≥50 mm
d≥500 mm
d≥500 mm
e≥20 mm
e≥100 mm
f≥600 mm
f≥500 mm
a≥10 mm
a≥50 mm
b≥300 mm
b≥100 mm
c≥10 mm
c≥50 mm
d≥500 mm
d≥500 mm
e≥20 mm
e≥100 mm
a≥10 mm
a≥50 mm
b≥500 mm
b≥500 mm
c≥10 mm
c≥50 mm
d≥500 mm
d≥500 mm
e≥20 mm
e≥100 mm
f≥900 mm
f≥600 mm
h
2
F
(mm)
ABCD Sides along the installation site with obstacles
F Front side
Suction side
In case of an installation site where sides A+B+C+D have
obstacles, the wall heights of sides A+C have no impact on
service space dimensions. Refer to the figure above for impact
of wall heights of sides B+D on service space dimensions.
In case of an installation site where only the sides A+B have
obstacles, the wall heights have no influence on any indicated
service space dimensions.
b
e
e
d
b
c
e
d
a
a
b
c
A+B
a≥200 mm
b≥300 mm
a≥200 mm
b≥300 mm
e≥400 mm
h
1
RYYQ+RYMQ+RXYQ8~20T7Y1B
VRV IV System Air Conditioner
4P329765-1 – 2012.09
c
c