Дув hymn boards with app control (2-/10-line) (17 pages)
Summary of Contents for Phoenix Advanced pressure monitor II
Page 1
Advanced Pressure Monitor II and Central Display Rough-In Installation Guide...
Page 2
Accel, Phoenix, Phoenix Controls, Usage Based Controls, UBC, Celeris, Theris, Traccel, Zone Presence Sensor and ZPS are registered trademarks, and LabPro, MacroServer, MicroServer and Neutralizer are trademarks of Honeywell International, Inc. Phoenix Controls products are covered by one or more of the following U.S. patents: 5,251,665 5,304,093...
Table of Contents Section 1. Advanced Pressure Monitor II Rough-In Installation 1.1 Required Parts to be Supplied by the Installer ........1 1.2 Parts Included with Your Order .
Section 1. Advanced Pressure Monitor II Rough-In Installation For the Advanced Pressure Monitor II (APM2) to be installed correctly, the rough-in phase of the project must be completed properly. This section will outline the specific considerations the General Contractor must pay attention to so that the final wiring and commissioning will go smoothly.
Each pressurization zone should have either a dedicated single-phase primary circuit, or a secondary circuit disconnect. • Refer to Phoenix Recommended Cables on page 33 for approved cable manufacturers and wire types. • Use stranded wire for ease of installation.
Advanced Pressure Monitor II Rough-In Installation Installation Overview • Strip 0.25" (6.4 mm) of insulation from each conductor, twist the strands, insert the conductor fully into the terminal block, and tighten the terminal. •Test the wire connection by pulling on each conductor.
(remote) transducer for the second room, or two external remote transducers may be used and wired to the analog inputs in the back of the unit. See Phoenix Recommended Cables on page 33 for approved cable manufacturers and wire types. NOTE: Layout the system in terms of wiring: •...
Advanced Pressure Monitor II Rough-In Installation Plumbing (Finish) 1.3.5 Remote Annunicator If an remote annunciator will be used, then mount a single gang electrical box in the desired location and run wires to it. Green LED Audible Alarm Red LED...
Advanced Pressure Monitor II Rough-In Installation Wiring Attach pressure tubing as follows: 1. Install the supplied silicone tube (with integrated spring) and attached barbed tube adaptor onto the end of the 0.25 field tubing. Thread the tubes, with installed adaptor, through the conduit opening at the bottom of the electrical box.
Advanced Pressure Monitor II Rough-In Installation Wiring ANALOG (ANL) OUTPUT POWER Earth Ground Current Output (4-20 mA) Voltage Output (0-5 Vdc, 0-10 Vdc) 24 Vac 24 Vac INPUTS (wired to door N.O. contact) RELAY Door Digital Input +15 Vdc Analog Input2...
APM2 Rough-In Installation Guide Advanced Pressure Monitor II Rough-In Installation Wiring 1.5.3 Analog Input, Labeled DOOR, INPUT2, INPUT1 There are two analog inputs available for remotely mounted transducer inputs. These are INPUT1 and INPUT2. A 15 Vdc (14.8 to 15.2) excitation is available to power up to two transducers. They can source 90 mA max.
Advanced Pressure Monitor II Rough-In Installation Wiring 1.5.5 Relay and Annunciator Output, Labeled RELAY There is an SPDT dry contact available. When an alarm occurs the Normally Open (NO) and the Common (COM) internal contacts will be closed. During no alarm conditions the Normally Closed (NC) and COM are shorted.
APM2 Rough-In Installation Guide Advanced Pressure Monitor II Rough-In Installation Wiring 1.5.7 Third Party Remote Annunciator The APM2 can drive other annunciators that are powered by a 15V supply, 50 mA max current draw, and accept a 15V trigger. If purchased separately, the Remote Annunciator can also be driven as shown below.
Page 16
Advanced Pressure Monitor II Rough-In Installation Wiring Mounting APM2 in Triple Gang Electrical Box Figure 1-11. 4. Mount the front cover assembly. Installed APM2 Figure 1-12. MKT-0262 MPC-1748 Rev 02/13...
Section 2. Fitting an APM2 in an APM100 Enclosure 2.1 Overview APM100 pressure monitors from Phoenix Controls can be replaced in the field using the newer APM2 units. However, it is important to order the Retrofit Kit version of the APM2 product for compatibility with the existing enclosure.
Fitting an APM2 in an APM100 Enclosure Instructions 2.2 Instructions As part of the site preparation, any wiring or tubing coming into the APM100 unit may IMPORTANT: need to be moved to accomodate the depth of the APM2. APM100 Display Figure 2-1.
APM2 Rough-In Installation Guide Fitting an APM2 in an APM100 Enclosure Instructions 2.2.2 Ensure Existing APM1 Enclosure Is Prepared For APM2 Unit 1. Make sure the wall surface around the existing enclosure is flat and clean with no wall damage or holes beyond the electrical box.
The back of the APM2 has electrical connectors labeled with their function. The mating electrical connectors (supplied) are color coded and labeled with the matching function. Refer to the Advanced Pressure Monitor II User’s Guide (MKT-0263) for detailed wiring instructions. 2.2.5 Remotely Switching Alarm Setpoints...
Figure 2-5. 2.2.7 Complete the Installation 1. Complete the installation following the instructions in the Advanced Pressure Monitor II User’s Guide (MKT-0263), which can be obtained from the Partner Login area of http://www.phoenixcontrols.com/. 2. Once wiring and pressure tubes are connected, verify functionality of the APM2 before sliding it into the wall enclosure.
Page 22
Fitting an APM2 in an APM100 Enclosure Instructions 4. Mount the front cover assembly. Installed APM2 Figure 2-7. MKT-0262 MPC-1748 Rev 02/13...
Triple gang-double deep electrical box (RACO 697 or Appleton M3-350), quantity 1 • Green grounding screw, quantity 1 • Power (18 AWG recommended) and signal wiring (22 AWG recommended), as needed. Refer to Phoenix Recommended Cables on page 33. • EMT conduit (if required by local code) •...
Each pressurization zone should have either a dedicated single-phase primary circuit, or a secondary circuit disconnect. • See Phoenix Recommended Cables on page 33 for approved cable manufacturers and wire types. • Use stranded wire for ease of installation. •...
APM2 Rough-In Installation Guide APM2 Central Display Rough-In Installation Installation Overview • Strip 0.25" (6.4 mm) of insulation from each conductor, twist the strands, insert the conductor fully into the terminal block, and tighten the terminal. •Test the wire connection by pulling on each conductor. WARNING: Wiring must be performed by a licensed electrician according to local and state codes.
APM2 Central Display Rough-In Installation Wiring 3.4 Wiring POWER Earth Ground 24 Vac 24 Vac COMM BACnet Communications (See Detail A) B (+) A (-) COMM B (+) DATA + A (-) DATA - DETAIL "A" GROUND SHIELD - ONE END ONLY REAR VIEW Rear View of the APM2 Central Display Showing Wiring Connections Figure 3-3.
APM2 Rough-In Installation Guide APM2 Central Display Rough-In Installation Wiring 3.4.2 Completing the Finish Wiring 1. Connect all the electrical connectors matching the wiring connector with the mates on the back of the unit. Connectors are color coded and keyed. 2.
Page 28
APM2 Central Display Rough-In Installation Wiring THIS PAGE INTENTIONALLY LEFT BLANK. MKT-0262 MPC-1748 Rev 02/13...
APM2 Rough-In Installation Guide Ancillary Product Specifications Model 264 Pressure Transducer Section 4. Ancillary Product Specifications The following specifications are subject to changes without notice. NOTE: 4.1 Model 264 Pressure Transducer Table 1. Model 264 Pressure Transducer (Remote Transducer 0-5 V Output) Model 264 Pressure Transducer Performance Data Standard...
Page 30
Ancillary Product Specifications Model 264 Pressure Transducer Pressure Fittings 3/16" OD barbed brass pressure fitting for 1/4" push-on tubing Zero and Span Adjustments Accessible on top of case Weight (approximate) 10 ounces Pressure Media Typically air or similar non-conducting gases Electrical Data—Voltage Circuit 3-wire (Com, Exc, Out)
Page 31
APM2 Rough-In Installation Guide Ancillary Product Specifications Model 264 Pressure Transducer #6 SCREW R0.078 in. TYP . WIRE CLAMP (R1.98 mm) TOP VIEW 3 PLACES 0.312 in. TYP . (7.92 mm) 2.750 in. (69.85 mm) 1.662 in. TYP . 0.385 in. (42.21 mm) TYP .
Page 34
Ancillary Product Specifications Model 267 Pressure Transducer 6.10 in. (155 mm) 5.60 in. (142 mm) 0.18 in. (Ø4.5 mm) 2.68 in. 0.75 in. (68 mm) (19 mm) 1.34 in. (34 mm) 0.50 in. (13 mm) 3/16" O.D. PRESSURE FITTING FOR 1/4" PUSH-ON TUBING 0.80 in.
Ancillary Product Specifications Pressure Pickup Port 4.4 Pressure Pickup Port Table 4. Pressure Pickup Port Cover Stainless steel standard wall cover plate Mounting Standard single gang electrical box (2 screws included) Dimensions 2.77" (70.23 mm) W x 4.52" (114.78 mm) H x 1.02" (26.08 mm) D Pressure Fitting 1/4"...
Page 42
Model 267 Electrical Data Included Parts 2, 19 Current 29 0.25" O.D. Tubes 2 Voltage 29 Advanced Pressure Monitor II 2, 19 Model 267 Environmental Data 28 APM2 2, 19 Model 267 Performance Data 28 Barbed Couplings 2 Model 267 Physical Description 28...
Page 43
APM2 Rough-In Installation Guide Pressure Pickup Port 1, 4, 32 Room Side 14 Turn Off Power 14 Pressure Pickup Port Installation 5 Pressure Signals 5, 11 Pressure Taps 17 Pressure Transducer Use of External Transducers 5 Model 264 25 Model 267 28 Pressure Tubing 14 Voltage Model 264 Electrical Data 26...
Page 44
THIS PAGE INTENTIONALLY LEFT BLANK. IX-4 MKT-0262 MPC-1748 Rev 02/13...
Need help?
Do you have a question about the Advanced pressure monitor II and is the answer not in the manual?
Questions and answers