Installation Instructions
6. Install the alarm on the mounting bracket and rotate the
alarm in the direction of the "ON" arrow on the cover until
the alarm ratchets into place (this ratcheting function allows
for aesthetic alignment). Note: The alarm will mount to the
bracket in 4 positions (every 90 degrees).
7. Turn on the AC power. The green AC Power On Indicator
should be lit when the alarm is operating from AC power.
8. Install batteries, close battery door.

Step 4: Testing the Alarm

!
CAUTION: Due to the loudness (85 decibels) of the
alarm, always stand an arms length away from the
unit when testing.
After installation, TEST THE UNIT'S ELECTRONICS by pressing
and releasing the test/reset button. You will then hear the
following sequence of "beeps" and verbal warnings:
Three long beeps.
Verbal warning: "FIRE!"
Three long beeps.
Four quick beeps.
Verbal warning: "WARNING! CARBON MONOXIDE"
Four quick beeps
Single beep to reset
Weekly testing is required! If at anytime it does not perform as
described, verify power is connected correctly and that the
battery doesn't need replacing. Clean dust and other buildup
off the unit. If it still doesn't operate properly call the Product
Support Line at 1-800-880-6788.