Loose Battery Models; Initial Testing And Checking Of Alarm - Kidde Slick 1SF23/9HI Installer's Manual

Smoke and heat alarm, 230v interconnectable mains operated alarms
Hide thumbs Also See for Slick 1SF23/9HI:
Table of Contents

Advertisement

1385-7202-06_W_V1:-

5. Loose Battery Models

• The alarm will not locate without a battery in the compartment
Never remove or connect cable harness, without having disconnected mains power, or
arcing could occur, damaging the alarm.
On rechargeable models there is no battery compartment -
Reinstall on alarm base plate affix to ceiling and push (and hold) test button to
verify battery operation.
Battery Changing
Loose battery models (battery charging) See section 12
Reconnect mains supply and check green L.E.D. is lit – red L.E.D. will flash intermit-
tently.
GREEN LED

6. Initial Testing and Checking of Alarm

Before powering up/testing CHECK THAT WIRING POLARITY is correct & all con-
nections are tight. REVERSING POLARITY will fatally damage all interconnected
alarms, and damage is not covered by the Guarantee. Slide alarm fully home on
base plate before powering up, to prevent arcing across the contact blades.
Having energised circuit, press and hold the test button again – the alarm should
sound and other interconnected ones also, within a few seconds.
Do this for all alarms.
If any do not sound, isolate mains and recheck cabling.
On optical alarms, if the red L.E.D. blinks every 30-40 seconds and the alarm
chirps in between, it indicates failure of the sensing chamber - replace alarm.
{This condition also exists if the Hush button is pushed}
Advise the house-holder (if present) as to how to test the alarms.