Toshiba MMD-AP0074SPH-E Installation Manual page 10

Air conditioner multi type
Hide thumbs Also See for MMD-AP0074SPH-E:
Table of Contents

Advertisement

SMMS Slim Duct Type
Attached hose
VP25 vinyl chloride pipe
Drain pipe
band
(locally procured)
connecting port
(Hard socket)
Attached flexible hose
Socket for VP25
Soft socket
(locally procured)
Hard socket
Adhesive inhibited:
Use the attached flexible hose and hose band for
connecting the drain hose to the clear drain socket.
If applying the adhesive, socket will be damaged and
cause water leakage.
Align the attached hose band to
the end of hose, set the
tightening position upward, and
Drain pipe
then tighten it.
connecting port
(Transparent)
VP25 vinyl
Flexible hose
chloride pipe
(Accessory)
(locally procured)
Socket for VP25 vinyl chloride pipe
(locally procured)
Connecting drain pipe
• Connect a hard socket (locally procured) to the hard
socket of the attached supplied flexible hose.
• Connect a drain pipe (locally procured) to the
connected hard socket.
REQUIREMENT
• Connect hard vinyl chloride pipes securely using an
adhesive for vinyl chloride to avoid water leakage.
• It takes some time until the adhesive is dried and
hardened (refer to the manual of the adhesive). Do not
apply stress to the joint with the drain pipe during this
time period.
17-EN
Installation Manual
Drain up
When a down-gradient cannot be secured for the
drainpipe, drain-up piping is possible.
• The height of the drain pipe must be 850 mm or less
from the bottom of the ceiling.
• Take the drain pipe out of the drain pipe joint with the
indoor unit in 300 mm or less, and bend up the pipe
vertically.
• Immediately after the pipe is bent up vertically, lay
the pipe making a down-gradient.
• Set downward grading immediately after raising up
vertically.
300 mm or less
Indoor unit
Underside of ceiling
Check the draining
In the test run, check that water drain is properly
performed and water does not leak from the connecting
part of the pipes.
Check draining also when installed in heating period.
By using a pitcher or hose, pour water (1500 - 2000 cc)
into the discharge port before installation of the ceiling
panel.
Pour water gradually so that water does not spread on
the motor of the drain pump.
CAUTION
Pour water gently so that it does not spread around
inside the indoor unit, which may cause a malfunction.
SMMS Slim Duct Type
– 9 –
Insert the edge of hose into the
drain pan and bend it downward.
CAUTION
Pour water gently so that it does not spread around inside the indoor unit, which may cause a malfunction.
• After the electric work has finished, pour water
during COOL mode operation.
• If the electric work has not yet finished, pull out the float switch connector (CN34: Red) from the electrical control
box, and check draining by plugging the single phase 220 - 240 V power to the terminal blocks R (L) and S (N).
If doing so, the drain pump motor operates.
• Test water drain while checking the operation sound of the drain pump motor.
(If the operation sound changes from continuous sound to intermittent sound, water is normally drained.)
After the check, the drain pump motor runs, connecting the float switch connector.
(In case of check by pulling out the float switch connector, be sure to return the connector to the original position.)
CN34
(RED)
Installation Manual
Cover plate
Pump
Vessel
Water
(1500 cc ~ 2000 cc)
220 - 240 V, 50 Hz
220 V, 60 Hz
Power
terminals
L
N
White
Red
Black
Pull out connector CN34 (Red)
from P.C. board.
Black
18-EN