Toshiba MMD-AP0054SPH-E Installation Manual

Multi type indoor unit
Hide thumbs Also See for MMD-AP0054SPH-E:

Advertisement

Quick Links

AIR CONDITIONER (MULTI TYPE)
Installation Manual
Indoor Unit
For commercial use
Model name:
Slim Duct Type
MMD-AP0054SPH-E
MMD-AP0074SPH-E
MMD-AP0094SPH-E
MMD-AP0124SPH-E
MMD-AP0154SPH-E
MMD-AP0184SPH-E
English

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba MMD-AP0054SPH-E

  • Page 1 AIR CONDITIONER (MULTI TYPE) Installation Manual Indoor Unit For commercial use Model name: Slim Duct Type MMD-AP0054SPH-E MMD-AP0074SPH-E MMD-AP0094SPH-E MMD-AP0124SPH-E MMD-AP0154SPH-E MMD-AP0184SPH-E English...
  • Page 2: Table Of Contents

    – 1 – Contents Original instruction Please read this Installation Manual carefully before installing the Air Conditioner. 1 Precautions for safety ..........3 •...
  • Page 3 Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
  • Page 4: Precautions For Safety

    – 3 – Precautions for safety  Warning indications on the air conditioner unit The manufacturer shall not assume any liability for the damage caused by not observing the description of this Warning indication Description manual. WARNING WARNING WARNING ELECTRICAL SHOCK HAZARD General ELECTRICAL SHOCK HAZARD Disconnect all remote...
  • Page 5 Installation Test run • Suction duct length must be longer than 850 mm. • Before operating the air conditioner after having completed the work, check that the electrical control box cover of the • When the indoor unit is to be suspended, the designated hanging bolts (M10 or W3/8) and nuts (M10 or W3/8) must indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position.
  • Page 6: Accessory Parts

    – 5 – Accessory parts Selection of installation place Avoid installing in the following places Part name Shape Usage Select a location for the indoor unit where the cool or warm air will circulate evenly. (Hand over to customers) Installation Manual This manual Avoid installation in the following kinds of locations.
  • Page 7: Installation Space

     Installation under high-humidity atmosphere  Service space (Unit: mm) In some cases including the rainy season, especially inside of the ceiling may become high-humidity atmosphere (dew-point temperature: 23 °C or higher). 1. Installation to inside of the ceiling with tiles on the roof 2.
  • Page 8: Installation

    – 7 – Installation  Arranging the to back air intake type <Back air intake> CAUTION Strictly comply with the following rules to prevent damage of the indoor units and human injury. • Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged) •...
  • Page 9  Installation of hanging bolt  Installation of indoor unit  Wireless remote controller • Consider the piping / wiring after the unit is hung to determine the location of the indoor unit installation and The sensor of indoor unit with wireless remote Treatment of ceiling orientation.
  • Page 10: Drain Piping

    – 9 – Drain piping  Drain up Align the attached Drain pipe hose band to the end VP25 vinyl chloride connecting of hose, set the pipe When a down-gradient cannot be secured for the port tightening position (Locally procured) drainpipe, drain-up piping is possible.
  • Page 11  Perform heat insulating Insert the edge of hose into the • As shown in the figure, cover the flexible hose and hose band with the attached heat insulator up to the bottom drain pan and bend it downward. of the indoor unit without gap. Cover plate •...
  • Page 12: Duct Design

    – 11 – Duct design Mount an air filter to the air intake side; otherwise decrease of capacity may be caused. <Under air intake> <Back air intake>  Arrangement (Unit: mm) Referring to the following dimensions, manufacture duct at the local site. Air filter Main unit <Under air intake>...
  • Page 13: Fan Characteristics

     Connecting method of the duct AP012 AP015 Standard air volume: 600 m Standard air volume: 690 m Heat insulator with sticking material (100 mm - width locally procured) Flange (locally procured) Connect a duct to the High (50 Pa) High (50 Pa) Aluminum tape (locally procured) inside of the flange...
  • Page 14 – 13 – ◆ Filter attached AP005 AP007 AP018 AP009 Standard air volume: 490 m Standard air volume: 540 m Standard air volume: 780 m High (50 Pa) Upper limit of external static pressure (50 Pa) Upper limit of High (50 Pa) High (50 Pa) external static pressure (50 Pa)
  • Page 15: Refrigerant Piping

    Refrigerant piping  Heat insulation process • Use the tightening torque levels as listed in the table below. Apply heat insulation for the pipes separately at liquid Projection margin in flaring: B (Unit: mm) Outer dia. of connecting side and gas side. Tightening torque (N•m) CAUTION pipe (mm)
  • Page 16: Electrical Connection

    – 15 – Electrical connection ▼ Power supply 220 V – 240 V ~, 50 Hz Power supply  Power supply wire and 220 V ~, 60 Hz WARNING Power supply switch / circuit breaker or power supply wiring / fuse rating for indoor units should be selected by the communication wires accumulated total current values of the indoor units.
  • Page 17: Wiring Between Indoor And Outdoor Units

     Wiring between indoor and outdoor units  Wire connection NOTE REQUIREMENT An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the • Connect the wires matching the terminal numbers. Incorrect connection causes a trouble. •...
  • Page 18: Applicable Controls

    – 17 – Applicable controls  Remote controller wiring Strip off approx. 9 mm the wire to be connected.  Basic procedure for changing REQUIREMENT ▼ Wiring diagram settings When the air conditioner is used for the first time, it will take some moments after the power has been turned on Terminal block for remote Terminal block...
  • Page 19  External static pressure settings Each time button is pushed, indoor unit numbers in the control group change cyclically. Select the indoor unit to change Set up a tap change based upon the external static pressure of the duct to be connected. settings for.
  • Page 20: Test Run

    – 19 – Test run  Filter sign setting  Remote controller sensor According to the installation condition, the filter sign The temperature sensor of the indoor unit senses room term (Notification of filter cleaning) can be changed. temperature usually. Set the remote controller sensor ...
  • Page 21: Maintenance

    Maintenance Wireless remote controller (TCB-AX32E2) <Daily maintenance> When TEMPORARY button is pushed for 10 seconds or more, “Pi!” sound is heard and ▼ Cleaning of air filter the operation changes to a forced cooling is displayed on the remote controller, maintain the air filter. operation.
  • Page 22 – 21 – Mount the air filter. Inspection before maintenance Attach the filter to the main unit while pushing the tabs Following inspection must be carried out by a qualified installer or qualified service person. Parts Inspection method Turn on the circuit breaker, then push the button on the remote controller to start the operation.
  • Page 23: Troubleshooting

    Troubleshooting  Confirmation and check  Confirmation of error log When an error occurred in the air conditioner, an error When an error occurred on the air conditioner, the error code and indoor UNIT No. appear on the display part log can be confirmed with the following procedure.
  • Page 24 – 23 – Check method On the wired remote controller, central control remote controller and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. board) to display the operation is provided.
  • Page 25 Check code Wireless remote controller Outdoor unit 7-segment display Sensor block display of receiving unit Check code name Judging device Wired remote AI-NET central controller display control display Auxiliary code Operation Timer Ready Flash — — Indoor unit TCJ sensor error Indoor unit —...
  • Page 26 – 25 – Check code Wireless remote controller Outdoor unit 7-segment display Sensor block display of receiving unit Check code name Judging device Wired remote AI-NET central controller display control display Auxiliary code Operation Timer Ready Flash — — Duplicated indoor units with priority (Displayed in indoor unit with priority) Duplicated indoor units with priority (Displayed in unit other than indoor unit No.
  • Page 27 Batch alarm of general-purpose equipment control interface Differs according to error contents of unit with occurrence of alarm Group control follower unit error TCC-LINK — — (L20 is displayed.) Decrease of No. of indoor units TCC-LINK: TOSHIBA Carrier Communication Link. 51-EN 52-EN – 26 –...
  • Page 28: Specifications

    Weight (kg) Main unit 336 Tadehara, Fuji-shi, Shizuoka-ken 416-8521 JAPAN Cooling Heating MMD-AP0054SPH-E MMD-AP0074SPH-E Authorized Nick Ball Representative / TCF Toshiba EMEA Engineering Director MMD-AP0094SPH-E holder: Toshiba Carrier UK Ltd. MMD-AP0124SPH-E Porsham Close, Belliver Industrial Estate, MMD-AP0154SPH-E PLYMOUTH, Devon, PL6 7DB. MMD-AP0184SPH-E...
  • Page 29 Warnings on Refrigerant Leakage Important Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant 2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening gas leaking out, its concentration will not exceed a set limit.
  • Page 30 – 29 – 57-EN 58-EN...
  • Page 31 EH99886799-1...