Faults
Fault inputs 1 – 4
Faults of external plant components can be communicated to the
central apartment unit by closing a contact. There are 4 fault inputs
available.
The fault inputs must have been activated when commission-
ing the plant, and the required input must be connected to the
central apartment unit so that the settings described here can
be made. For the relevant descriptions, refer to document
"Mounting and Commissioning (CE1C2707en)".
For each fault input, following can be selected or set:
• Fault text (text that shall be displayed at the respective fault
input when the fault occurs)
• Fault priority (urgent or Not urgent)
• Fault release (always or only during absence)
• Fault status message delay (time span 00.00 – 60.00 m.s.,
until a pending fault generates a fault status message)
• Normal position: It can be selected here whether an open or
closed contact shall be used to indicate a faulty condition.
Normally open means that an open contact will be considered
to indicate "normal operation"
Main menu > Settings > Faults > Fault input X > Fault text:
Main menu > Settings > Faults > Fault input X > Fault priority:
Main menu > Settings > Faults > Fault input X > Fault release:
Main menu > Settings > Faults > Fault input X >
Fault stat mess dly:
Main menu > Settings > Faults > Fault inputX > Normal position: