Carrier WeatherMaker 48TC Series Product Data page 90

Carrier gas heat/electric cooling packaged rooftop 3 to 15 nominal tons
Hide thumbs Also See for WeatherMaker 48TC Series:
Table of Contents

Advertisement

3. High pressure switch.
a. Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high
pressure switches. They shall physically prevent the cross- - wiring of the safety switches between circuits 1
and 2.
b. High pressure switch shall use different color wire than the low pressure switch. The purpose is to assist the
installer and service technician to correctly wire and or troubleshoot the rooftop unit.
4. Automatic reset, motor thermal overload protector.
5. Heating section shall be provided with the following minimum protections:
a. High temperature limit switches.
b. Induced draft motor speed sensor.
c. Flame rollout switch.
d. Flame proving controls.
23 09 93
Sequence of Operations for HVAC Controls
23 09 93.13
Decentralized, Rooftop Units:
23 09 93.13
INSERT SEQUENCE OF OPERATION
23 40 13
Panel Air Filters
23 40 13.13
Decentralized, Rooftop Units:
23 40 13.13.A.
Standard filter section
1. Shall consist of factory installed, low velocity, disposable 2- - in. thick fiberglass filters of commercially available
sizes.
2. Unit shall use only one filter size. Multiple sizes are not acceptable.
3. Filters shall be accessible through an access panel with "no- - tool" removal as described in the unit cabinet section
of this specification (23 81 19.13.H).
23 81 19
Self- - Contained Air Conditioners
23 81 19.13
Small- - Capacity Self- - Contained Air Conditioners (48TC**04- - 16)
23 81 19.13.A.
General
1. Outdoor, rooftop mounted, electrically controlled, heating and cooling unit utilizing a fully hermetic scroll com-
pressor(s) for cooling duty and gas combustion for heating duty.
2. Factory assembled, single- - piece heating and cooling rooftop unit. Contained within the unit enclosure shall be
all factory wiring, piping, controls, and special features required prior to field start- - up.
3. Unit shall use Puron refrigerant.
4. Unit shall be installed in accordance with the manufacturer's instructions.
5. Unit must be selected and installed in compliance with local, state, and federal codes.
23 81 19.13.B.
Quality Assurance
1. Unit meets ASHRAE 90.1 minimum efficiency requirements.
2. Unit shall be rated in accordance with AHRI Standards 210/240 and 340/360.
3. Unit shall be designed to conform to ASHRAE 15, 2001.
4. Unit shall be UL- - tested and certified in accordance with ANSI Z21.47 Standards and UL- - listed and certified
under Canadian standards as a total package for safety requirements.
5. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
6. Unit casing shall be capable of withstanding 500- - hour salt spray exposure per ASTM B117 (scribed specimen).
7. Unit shall be designed in accordance with ISO 9001, and shall be manufactured in a facility registered by ISO
9001.
8. Roof curb shall be designed to conform to NRCA Standards.
9. Unit shall be subjected to a completely automated run test on the assembly line. The data for each unit will be
stored at the factory, and must be available upon request.
10. Unit shall be designed in accordance with UL Standard 1995, including tested to withstand rain.
11. Unit shall be constructed to prevent intrusion of snow and tested to prevent snow intrusion into the control box
up to 40 mph.
12. Unit shake tested to assurance level 1, ASTM D4169 to ensure shipping reliability.
13. High Efficient Motors listed shall meet section 313 of the Energy Independence and Security Act of 2007 (EISA
2007)
23 81 19.13.C.
Delivery, Storage, and Handling
1. Unit shall be stored and handled per manufacturer's recommendations.
90

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents