Vent Run Support Requirements - Lennox ELITE LDV42N Installation Instructions Manual

Elite series linear view direct-vent gas fireplace
Table of Contents

Advertisement

LENNOX HEARTH PRODUCTS • ELITE LINEAR VIEW DIRECT-VENT GAS FIREPLACE (MODELS LDV42, LDV54) • INSTALLATION INSTRUCTIONS
VENTINg INSTALLATION
(CONTINUED)
VENT RUN SUPPORT
REqUIREMENTS
Supporting Vertical Vent Runs
Note: Proper venting support is very
important. NEVER use the fireplace to
support the weight of the venting.
Support the vertical portion of the venting
system every 8 feet (2.4 m) above the fire-
place vent outlet (see Figure 15-1).
Use Support Straps (cat. no. SV4.5SU;
see "Accessory" section in this manual) or
conventional plumber's tape (not provided).
Secure the plumber's tape to the framing
members with nails or screws. Loop the
plumber's tape around the vent, securing the
ends of the tape to the framing. Use #6 x
1/2" sheet metal screws to secure the support
straps to the vent pipe.
Blocking
Support Straps
(e.g., plumber's tape;
not provided)
Support vertical venting
every 8 feet (2.4 m) above
appliance vent outlet.
See "MINIMUM
CLEARANCES TO
COMBUSTIBLES"
in this manual.
Figure 15-1: Vertical Venting Support
Supporting horizontal Vent Runs
See Figure 15-2. Install support straps every
5 ft (1.524 m) along horizontal/inclined
vent runs using Use Support Straps (cat. no.
SV4.5SU; see "Accessory" section in this
manual) or conventional plumber's tape (not
provided).
horizontal
Support
Building
Brackets
Support
framing
90° Elbow
Ceiling
Vertical
Rise
Figure 15-2: Typical Horizontal Termination System
NOTE: DIAGRAMS AND ILLUSTRATIONS ARE REPRESENTATIVE AND ARE NOT DRAWN TO SCALE.
NOTICE:
horizontal runs on a steady, (i.e., no
"dips"), slightly positive incline of
approximately 1/4 inch rise-per-foot (20
millimeters rise-per-meter) horizontal,
in a direction away from the fireplace.
(Slightly smaller rise-per-foot run ratios
are acceptable.) Use a carpenter's level
to measure from a constant surface, and
adjust support straps as necessary.
horizontal/Inclined Run
Vertical
Place horizontal support brackets
firestop/
every 5 ft (1.524 m).
Spacer
u
Support vertical venting every
8 ft (2.4 m) above fireplace vent
outlet (see "Supporting Vertical
Vent runs" on this page).
fireplace
It is important to install
horizontal
firestop/
Spacer
Straight Vent
Sections
horizontal
Termination
Exterior
Min. 6" Vertical Section
Wall
and One 90° Elbow
horizontal
Termination
u
15